G15 auto/manual switch - 3 – Micromod Micro-DCI: 53MC5000 Multi-Loop Process Controller CUSTOMIZATION GUIDE User Manual
Page 45

G15
AUTO/MANUAL SWITCH - 3
INPUTS
NAME
SYMBOL
DATAPOINT
CONTROL OUTPUT
CO3
C231
AUTO ENABLE
AE3
L186
OUTPUT TRACK VALVE
OTV3
C237
OUTPUT TRACK SWITCH
SWOTV3
L189
PARAMETERS
OUTPUT TRACK ENABLE
OTE3
L191
HARD MANUAL LIMIT
HML3
L194
OUTPUT HIGH LIMIT
OH3
C217
OUTPUT LOW LIMIT
OL3
C218
OUTPUT SLEW RATE
T33
C226
OUTPUTS
OUTPUT
OUT3
C210
OUTPUT TRACK STATUS
OVTS3
L177
AUTO STATUS
AUT3
L179
Description:
The AUTO/MAN Switch selects one of three signals to load into OUT. The signal
selected is either the Output Tracking Value (OTV), the Auto Value (CO) or the
Manual Pushbutton Value. If the Output Tracking Switch (SWOUT) is zero (0) then
OUT = OTV when Output Tracking is enabled (OTE = 1). When the previous
condition is not in effect OUT will equal CO if Auto Enable = 1 and the A/M
pushbutton has set the Auto Switch to 1. When neither previous condition is in effect
the selected signal comes directly from the output increase and decrease pushbut-
tons.
MODULAR CONTROLLER CUSTOMIZATION GUIDE
2-38