F-cim 43 auto/manual switch - 0, Will equal s – Micromod Micro-DCI: 53MC5000 Multi-Loop Process Controller CUSTOMIZATION GUIDE User Manual
Page 61

F-CIM 43
AUTO/MANUAL SWITCH - 0
NOT REUSABLE
INPUTS
NAME
SYMBOL
DATAPOINT
S
n-1
CONTROL OUTPUT
CO0
C123
A
AUTO ENABLE
AE0
L114
B
OUTPUT TRACK VALVE
OTV0
C129
C
OUTPUT TRACK SWITCH
SWOTV0
L117
PARAMETERS
OUTPUT TRACK ENABLE
OTE0
L119
HARD MANUAL LIMIT
HML0
L122
OUTPUT HIGH LIMIT
OH0
C109
OUTPUT LOW LIMIT
OL0
C110
OUTPUT SLEW RATE
T30
C118
OUTPUTS
S
n
OUTPUT
OUT0
C102
OUTPUT TRACK STATUS
OVTS0
L105
AUTO STATUS
AUT0
L107
Description:
This module selects one of three signals to load into OUT and become its output
(S
n
). The signal selected is either the Output Tracking Value (B), the Auto Value
(S
n-1
) or the Manual Pushbutton Value. If the Output Tracking Switch (C) is less
than 1, then S
n
= B when Output Tracking is enabled (OTE = 1). When the pre-
vious condition is not in effect S
n
will equal S
n-1
if Auto Enable (A) is
≥1 and the
A/M pushbutton has set the Auto Switch to 1. When neither previous condition is
in effect the selected signal comes directly from the output increase and decrease
pushbuttons.
MODULAR CONTROLLER CUSTOMIZATION GUIDE
3-9