F-cim 73 auto/manual switch - 3, Will equal s – Micromod Micro-DCI: 53MC5000 Multi-Loop Process Controller CUSTOMIZATION GUIDE User Manual
Page 75

F-CIM 73
AUTO/MANUAL SWITCH - 3
NOT REUSABLE
INPUTS
NAME
SYMBOL
DATAPOINT
S
n-1
CONTROL OUTPUT
CO3
C231
A
AUTO ENABLE
AE3
L186
B
OUTPUT TRACK VALVE
OTV3
C237
C
OUTPUT TRACK SWITCH
SWOTV3
L189
PARAMETERS
OUTPUT TRACK ENABLE
OTE3
L191
HARD MANUAL LIMIT
HML3
L194
OUTPUT HIGH LIMIT
OH3
C217
OUTPUT LOW LIMIT
OL3
C218
OUTPUT SLEW RATE
T33
C226
OUTPUTS
S
n
OUTPUT
OUT3
C210
OUTPUT TRACK STATUS
OVTS3
L177
AUTO STATUS
AUT3
L179
Description:
This module selects one of three signals to load into OUT and become its output
(S
n
). The signal selected is either the Output Tracking Value (B), the Auto Value
(S
n-1
) or the Manual Pushbutton Value. If the Output Tracking Switch (C) is less
than 1, then S
n
= B when Output Tracking is enabled (OTE = 1). When the pre-
vious condition is not in effect S
n
will equal S
n-1
if Auto Enable (A) is
≥ 1 and the
A/M pushbutton has set the Auto Switch to 1. When neither previous condition is
in effect the selected signal comes directly from the output increase and decrease
pushbuttons.
MODULAR CONTROLLER CUSTOMIZATION GUIDE
3-23