G03 setpoint generator - 3 – Micromod Micro-DCI: 53MC5000 Multi-Loop Process Controller CUSTOMIZATION GUIDE User Manual
Page 33

G03
SETPOINT GENERATOR - 3
NAME SYMBOL
DATAPOINT
INPUTS
REMOTE SETPOINT
RSP3
C228
REMOTE SP ENABLE
RE3
L187
SETPOINT TRACK INPUT
STV3
C236
SETPOINT TRACK SWITCH
SWSPT3
L188
PARAMETERS
SETPOINT TRACK ENABLE
STE3
L190
REMOTE GAIN
K13
C221
REMOTE BIAS
B13
C220
INSTRUMENT RANGE
IR3
C223
SETPOINT HI LIMIT
SH3
C233
SETPOINT LOW LIMIT
SL3
C234
OUTPUTS
SETPOINT SP3
L209
SETPOINT TRACK STATUS
SPTS3
L176
REMOTE STATUS
RMT3
L180
Description:
This subroutine selects one of three signals to load into SP. The signal selected is
either the Setpoint Track Value (STV), the Remote Setpoint (RSP) after being
multiplied by K1 and biased by B1 or the Setpoint Pushbutton Value. If the Setpoint
Track Switch (SWSPT) is zero (0) then SP = STV when Setpoint Tracking is enabled
(STE=1). When the previous condition is not in effect SP will equal (RSP x K1) + B1
if Remote Enable = 1 and the R/L pushbutton has set the Remote Switch to 1. When
none of the previous conditions are in effect the signal comes directly from the
setpoint increase and decrease pushbuttons.
MODULAR CONTROLLER CUSTOMIZATION GUIDE
2-26