F-CIM 41
PID - 0

NOT REUSABLE

NAME

SYMBOL

DATAPOINT

INPUTS

S

n-1

DEVIATION

DV0

C121

A

[unused]

B

RESET FEEDBACK

RF0

C127

C

CONTROL TRACK COM-
MAND

CTC0

L123

PARAMETERS

PROPORTIONAL BAND

PB0

C106

RESET TIME

TR0

C107

RATE TIME

TD0

C108

OUTPUT HIGH LIMIT

OH0

C109

OUTPUT LOW LIMIT

OL0

C110

MANUAL RESET

MR0

C111

INSTRUMENT RANGE

IR0

C115

FEED FORWARD

FF0

C122

REVERSE SWITCH

RSW0

L106

OUTPUTS

S

n

CONTROL OUTPUT

CO0

C123

Description:
This module computes a control output signal based on the above listed inputs and parameters.
The result is simultaneously available as the module output Sn and as a database parameter CO.
The A, B, and C inputs can be any L,B, C[S], or H type datapoint. When the control track command
(C) input is less than one, the module output will track the reset feedback input (B) by back calcu-
lating the integrator term. When (C) input is greater than or equal to 1 the reset feedback is used
by the integrator to calculate the next output and should reflect the value (scaled 0-100%) of the
value of the final control element. For standard PID controller reset feedback, (B) should be OUT
and control track command should be AUT.