F-cim 41 pid - 0 – Micromod Micro-DCI: 53MC5000 Multi-Loop Process Controller CUSTOMIZATION GUIDE User Manual
Page 60

F-CIM 41
PID - 0
NOT REUSABLE
NAME
SYMBOL
DATAPOINT
INPUTS
S
n-1
DEVIATION
DV0
C121
A
[unused]
B
RESET FEEDBACK
RF0
C127
C
CONTROL TRACK COM-
MAND
CTC0
L123
PARAMETERS
PROPORTIONAL BAND
PB0
C106
RESET TIME
TR0
C107
RATE TIME
TD0
C108
OUTPUT HIGH LIMIT
OH0
C109
OUTPUT LOW LIMIT
OL0
C110
MANUAL RESET
MR0
C111
INSTRUMENT RANGE
IR0
C115
FEED FORWARD
FF0
C122
REVERSE SWITCH
RSW0
L106
OUTPUTS
S
n
CONTROL OUTPUT
CO0
C123
Description:
This module computes a control output signal based on the above listed inputs and parameters.
The result is simultaneously available as the module output Sn and as a database parameter CO.
The A, B, and C inputs can be any L,B, C[S], or H type datapoint. When the control track command
(C) input is less than one, the module output will track the reset feedback input (B) by back calcu-
lating the integrator term. When (C) input is greater than or equal to 1 the reset feedback is used
by the integrator to calculate the next output and should reflect the value (scaled 0-100%) of the
value of the final control element. For standard PID controller reset feedback, (B) should be OUT
and control track command should be AUT.
MODULAR CONTROLLER CUSTOMIZATION GUIDE
3-8