F-cim 74 setpoint generator - 3, Will equal s – Micromod Micro-DCI: 53MC5000 Multi-Loop Process Controller CUSTOMIZATION GUIDE User Manual
Page 76

F-CIM 74
SETPOINT GENERATOR - 3
NOT REUSABLE
NAME
SYMBOL
DATAPOINT
INPUTS
S
n-1
REMOTE SETPOINT
RSP3
C228
A
REMOTE SP ENABLE
RE3
L187
B
SETPOINT TRACK INPUT
STV3
C236
C
SETPOINT TRACK SWITCH
SWSPT3
L188
PARAMETERS
SETPOINT TRACK ENABLE
STE3
L190
REMOTE GAIN
K13
C221
REMOTE BIAS
B13
C220
INSTRUMENT RANGE
IR3
C223
SETPOINT HI LIMIT
SH3
C233
SETPOINT LOW LIMIT
SL3
C234
OUTPUTS
S
n
SETPOINT
SP3
C209
SETPOINT TRACK STATUS
SPTS3
L176
REMOTE STATUS
RMT3
L180
REMOTE SWITCH
SWR3
L185
Description:
This module selects one of three signals to load into SP and become its output
(S
n
). The signal selected is either the Setpoint Tracking Value (B), the Remote
Setpoint Value (S
n-1
) multiplied by K1 and biased by B1, or the Setpoint pushbut-
ton value. If the Setpoint Track Switch (C) is less than 1, then S
n
=B when Setpoint
Tracking is enabled (STE=1). When the previous condition is not in effect S
n
will
equal S
n-1
x K1 + B1 if RemoteEnable (A) is greater than or equal to 1 and the
R/L pushbutton has set Remote Switch to1. When none of the previous conditions
are in effect the selected signal comes directly from the setpoint increase and de-
crease pushbuttons.
MODULAR CONTROLLER CUSTOMIZATION GUIDE
3-24