G07 deviation/alarm calculation - 3 – Micromod Micro-DCI: 53MC5000 Multi-Loop Process Controller CUSTOMIZATION GUIDE User Manual
Page 37

G07
DEVIATION/ALARM CALCULATION - 3
INPUTS
NAME
SYMBOL
DATAPOINT
SETPOINT
SP3
C209
PROCESS VARIABLE
PV3
C208
PARAMETERS
SETPOINT SLEW RATE
T13
C225
CONTROL ZONE
CZ3
C222
ALARM INDEX
AIX3
B350
ALARM LIMIT 1
PL13
C211
ALARM LIMIT 2
PL23
C212
ALARM DEADBAND
ADB3
C213
OUTPUTS
DEVIATION
DV3
C229
ALARM A
PA13
L182
ALARM B
PA23
L183
Description:
This subroutine calculates and loads the deviation value based on setpoint (SP) and
process variable (PV). Before the calculation is performed the setpoint value is
conditioned so as not to exceed the rate of change limit specified by T1. If the
calculated deviation falls within the CZ value, then deviation is forced to 0.0. This
module also determines if alarm conditions exist based on AIX, PL1, PL2 and ADB.
Results of the alarm tests are loaded to PA1 and PA2. Refer to Section 4.1.6 of
Instruction Bulletin 53MC5000 for an explanation of AIX values.
MODULAR CONTROLLER CUSTOMIZATION GUIDE