ommend that you document the final positions of all jumpers by marking them on the
drawing above (or a copy of it) The jumpers are:

A) Latched E-Stop

This is the only jumper that is not related to the fifteen individual safety

inputs.

Latched E-Stop

Yes

Latched E-Stop

No

In the ʻYesʼ position, if a show is started while there is an E-Stop condition

still present, the Kp-300 will not allow you to enable the

Blocking Valve Out-

put

until the show has finished, even if the E-Stop input is cleared. This al-

lows you to safely run test shows without movement after an E-Stop10.

If this jumper is in the ʻNoʼ position, if a show is started while there is an

E-Stop condition still present, the Kp-300 will allow you to enable the

Block-

ing Valve Output

once the E-Stop input is cleared. This means that the

movement may be enabled by the

Blocking Valve Output

part way through a

show when the E-Stop condition is cleared.

B) Internal/External Power

(One set of jumpers for each safety input and one set for the

Remote Log Belt

Input

)

Sixteen sets of jumpers in total

External Power

Internal Power

The fifteen Safety Inputs and one

Remote Belt Log Input

are optically iso-

lated to 1500 volts. This jumper sets whether the optoisolators use the same
power as the Kp-300 or if you must provide them with an external source of
24 vdc power. Use the Internal Power if you are going to be attaching these
inputs to a simple switch closures. Use the External setting if you are using a
device that provides power.

When possible try to use external power. When doing so, a high voltage

spike on an externally powered input line cannot get into the Kp-300 and
damage it.

Gilderfluke & Co.• 205 South Flower Street • Burbank, California 91502 • 818/840-9484 • 800/776-5972 • fax 818/840-9485

Kp-300 Manual / September 4, 2012 4:29 PM / page 28 of 75

10 # Assuming that the

Blocking Valve Output

is used in the installation.