LEESON Micro Series Compact Inverters User Manual
Page 17

15
460 VOLT MICRO SERIES RATINGS
MODEL
INPUT OUTPUT
(400/480 Vac, 50-60 Hz)
(0-400/460 Vac)
FOR MOTORS
NOMINAL
NOMINAL
CATALOG
RATED
INPUT
CURRENT
POWER
CURRENT POWER
NUMBER
HP
kW
PHASE
(AMPS)
(KVA)
(AMPS)
(KVA)
174920
174939*
1
0 .75
3
2 .8/2 .4
2 .0
2 .3/2 .0
1 .6
174532**
174921
174940*
2
1 .5
3
4 .7/4 .1
3 .4
3 .9/3 .4
2 .7
174533**
174922
174941*
3
2 .2
3
6 .8/5 .7
4 .7
5 .5/4 .8
3 .8
174534**
174923
174942*
5
3 .7
3
10 .2/8 .9
7 .3
8 .7/7 .6
6 .1
174535**
174924
174548*
7 .5
5 .5
3
14 .7/12 .8
10 .6
12 .6/11 .0
8 .8
174745**
174552
174554*
10
7 .5
3
18 .3/15 .9
13 .2
16 .0/14 .0
11 .2
174747**
174558
174749*
15
11
3
28/24
19 .8
24/21
16 .7
174750**
174561
174752*
20
15
3
36/31
25 .3
31/27
21 .5
174753**
174563
25 18 .5 3 44/38 31 .9 39/34 27 .1
174755*
174565
30 22
3 52/45 37 .6 46/40 31 .9
174757*
174567
40 30
3 68/59 49 .0 60/52 44 .0
174513*
174593
50 37
3 85/74 61 .5 75/65 51 .8
174511*
174572
60 45
3 100/87 72 .3 88/77 61 .3
174574*
174580
75
55
3 109/91 75 .5 110/96 76 .5
174581*
174582
100
75
3 139/116 96 .4 143/124 98 .8
174583*
174584
125
90
3 175/146 121 .4 179/156 124 .3
174585*
174586
150
110
3
202/168
139 .7
207/180
143 .4
NOTE See Section 8 .0 for recommended fuse type .
* = NEMA 4/12 or 12 ENCLOSURE
** = NEMA 4X ENCLOSURE