0 keypad control – LEESON Micro Series Compact Inverters User Manual
Page 30

3. If the motor is rotating in the wrong direction, press the “STOP” key, remove power from the
drive, wait three minutes for the bus capacitors to discharge, and swap any two of the motor wires
connected to T1, T2, and T3 .
NOTE 1:
The drive is phase insensitive with respect to incoming line voltage . Therefore, to change the
motor rotation, the phases must be swapped at the drive output terminals or at the motor .
NOTE 2:
If the drive’s display is blank after power up, and it is a model equipped with heatsink fans, check
to make sure the fans are operating (they should be spinning anytime power is applied to the drive). If they
are not spinning, the drive’s display will be blank and the drive cannot be operated. If the fans are clogged
or jammed, disconnect power from the drive and remove any obstructions from the fans. Reapply power
to the drive and check the fans. If they are spinning, the drive’s display should appear and the drive should
operate properly . If there are no obstructions, the fan itself may be defective . Please contact the factory for
assistance .
13.0 KEYPAD CONTROL
The drive can be operated in a number of different ways: keypad (LOCAL), control devices wired to the
terminal strip (REMOTE), or a combination of the terminal strip and the keypad. The drive should first
be operated from the keypad during initial start-up. Refer to Sections 14.0 - CONTROL WIRING, and
18 .0 - DESCRIPTION OF PARAMETERS for information on remote operation .
13.1 KEYPAD FUNCTIONS
START/STOP
To start the drive, press the START key. To stop the drive, press the STOP
key.
NOTE:
The STOP key is active in both LOCAL and REMOTE modes.
SPEED set point
To increase the speed set point, press the UP arrow key. To decrease the
speed set point, press the DOWN arrow key.
FORWARD/REVERSE
To change rotation direction, press the FWD/REV key and then press the
ENTER key within three seconds.
NOTE:
Parameter 27 - ROTATION must be set to FWD & REV for this
key to be active.
AUTO/MANUAL
To toggle between AUTOMATIC (terminal strip) and MANUAL (key-
pad) speed control, press the AUTO/MAN key and then press the ENTER
key within three seconds.
NOTE:
Parameter 28 - AUTO/MAN must be set to BOTH for this key
to be active . See Section 14 .0 - CONTROL WIRING for information on
automatic speed references .
FAULT RESET
Use the STOP key to reset a fault. If the fault condition has passed,
pressing the STOP key will reset the fault and return the drive to a STOP
condition .
NOTE:
If an OUTPUT fault occurs, there will be a 30 second delay before
the fault can be cleared using the STOP key.
28