LEESON Micro Series Compact Inverters User Manual

Page 59

Advertising
background image

The “speed-compensated” thermal overload circuit offers additional protection from high load conditions

at low speeds, where motor cooling is often less effective (e.g., motors with shaft-mounted fans). As seen on

the diagram below, the drive reduces the allowable continuous output current when operating at frequencies

less than 30 Hz.

Example 2:

A 480 Vac, 20 HP drive is operating a motor at 10 Hz. From the diagram, a drive operating at

10 Hz can deliver about 75% of its output current rating continuously. A 480 Vac, 20 HP drive’s output

current rating is 27 Amps . Therefore, the drive would be able to operate continuously at 20 Amps . The

drive would also be able to deliver 150% of that value (30 Amps) for one minute before tripping into an

OVERLOAD fault .

The “speed compensated” thermal overload is the factory default and should be used in applications where

the motor does not normally experience high loads at low speeds for extended periods of time.

NOTE 1:

The above diagram is based on a MOTOR OL setting of 100% . For lower MOTOR OL settings,

reduce the % CURRENT values by the same percentage. For example, if MOTOR OL is set to 75%, reduce

the % CURRENT values by 25% . Therefore, the curve shifts down, but the shape of the curve remains the

same .

The “non-compensated” thermal overload circuit allows 100% current continuously, and 150% current

for one minute, at all speeds. In the example above, the motor operating at 10 Hz without

“speed-compensated” protection would be allowed to operate continuously at 27 Amps, and could draw

40 .5 Amps for one minute before tripping . Without sufficient motor cooling, this can result in motor

failure due to overheating .

The “non-compensated” circuit is selected by setting Parameter 22 - TORQUE to CT/NOCMP. The

“non-compensated” setting should only be used in applications where the motor is properly cooled at all

speeds, or the motor manufacturer has approved the motor for full-load operation at low speeds .

NOTE 2:

The operation of the motor thermal overload circuit is affected by the setting of Parameter 34 -

LOAD MLT .

57

NON-COMPENSATED

SPEED COMPENSA

TED

100

80

60

40

20

10

20

30

40

50

60

FREQUENCY (Hz)

MAXIMUM CONTINUOUS OUTPUT CURRENT (%

)