14.2.4 THREE-WIRE START/STOP CONTROL
A three-wire start/stop circuit can be accomplished by one of two methods on the MICRO Series drive .
Follow the appropriate procedure listed below:
FORWARD ROTATION ONLY
1. Select REMOTE mode (see 14.2.1).
2 . Wire a normally closed momentary STOP contact between TB-1 and TB-2 .
Momentarily open this contact to STOP the drive .
3 . Wire a normally open momentary START contact between TB-12A and TB-2 . Momentarily close
this contact to START the drive .
FORWARD and REVERSE ROTATION with TWO START CONTACTS
1. Select REMOTE mode (see 14.2.1).
2 . Program Parameter 27 - ROTATION to FWD & REV .
3 . Program Parameter 49 - TB13C to START REVERSE .
4 . Wire a normally closed momentary STOP contact between TB-1 and TB-2 . Momentarily open
this contact to STOP the drive .
5 . Wire a normally open momentary START FORWARD contact between TB-12A and TB-2 .
Momentarily close this contact to START the drive in FORWARD .
6 . Wire a normally open momentary START REVERSE contact between TB- 13C and TB-2 .
Momentarily close this contact to START the drive in REVERSE .
NOTE:
If the drive is operating in one direction, and is given the START command for the opposite
direction, the drive will decelerate to 0 Hz and then accelerate back to the speed set point in the opposite
direction .
FORWARD and REVERSE ROTATION with ONE START CONTACT
1 . Follow 1-4 above and wire a normally open momentary contact between TB-2 and the common of a
single-pole, double-throw toggle switch . Wire the poles of the toggle switch to TB-12A and TB-13C .
Refer to the wiring diagram in Section 15 .3 .