LEESON Micro Series Compact Inverters User Manual

Page 41

Advertising
background image

JOG

The JOG function only works when the drive is in REMOTE mode, and only when the drive is in a STOP

condition. TB-13B can be programmed for either JOG FORWARD or JOG REVERSE. The jog speed is

set by PRESET SPEED #2. Close TB-13B to TB-2 to JOG, and open the contact to STOP.

When operating in JOG mode, the STOP key WILL NOT stop the drive. To stop the drive,

the contact between TB-13B and TB-2 must be opened .

MOP - MOTOR OPERATED POT

TB-13A and TB-13B are used for this function, which sets the speed of the drive using contacts wired

to the terminal strip . Set TB-13A for DEC FREQ, and set TB-13B for INC FREQ . Closing TB-13A to

TB-2 will activate the DEC FREQ function, and will cause the speed set point to decrease until the contact

is opened . DEC FREQ will operate when the drive is in RUN mode or STOP mode . Closing TB-13B to

TB-2 will activate the INC FREQ function, and will cause the speed set point to increase until the contact

is opened . INC FREQ will only operate when the drive is in RUN mode .

NOTE:

If TB-13A, TB-13B, and TB-13C are all programmed for speed references, and two or three of

the terminals are closed to TB-2, the higher terminal has priority and will override the others. For example,

if TB-13A is programmed for 0-10 VDC, and TB-13C is programmed for PRESET SPEED #1, closing

both terminals to TB-2 will cause the drive to respond to PRESET SPEED #1, because TB-13C overrides

TB-13A .

14.2.7 ANALOG OUTPUT SIGNALS

There are two terminals that can supply analog output signals proportional to output frequency or

load. Terminal TB-10A can provide a 0-10 VDC or a 2-10 VDC signal proportional to output frequency,

and TB-10B can provide the same signals proportional to load . The 2-10 VDC signals can be converted

to a 4-20 mA signal using a 500 ohms resistor in series with the signal . See Parameters: 42 - TB10A OUT,

43 - @TB10A, 44 - TB10B OUT, and 45 - @TB10B in Section 18 .0 - DESCRIPTION OF

PARAMETERS .

NOTE:

These analog output signals cannot be used with “loop-powered” devices that deride power from a

4-20 mA signal .

14.2.8 DRIVE STATUS OUTPUT CONTACTS

The control board has one FORM C relay at terminals TB-16, TB-17, and TB- 18 . Contacts are rated 2

amps at 28 VDC or 120 Vac .

There are also two open-collector outputs at terminals TB-14 and TB-15 . The open-collector circuit is a

current sinking type rated at 30 VDC and 40 mA maximum. An external power supply (30 VDC max)

must be used to power the open-collector outputs . The drive does not have a dedicated power supply for the

open-collector outputs .

The FORM C relay and the open collector outputs can be programmed to indicate any of the following:

RUN, FAULT, /FAULT (INVERSE FAULT), LOCK (FAULT LOCKOUT), AT SPEED, ABOVE #3,

I LIMIT (CURRENT LIMIT), or AUTO/MAN. See Parameters: 52 - TB14 OUT, 53 - TB15 OUT, and

54 - RELAY . Refer to Section 6 .2 .5 for a complete description of each of these status indications .

39

WARNING

Advertising