65 PROGRAM

(PROGRAM FACTORY DEFAULTS)

STOP (TB-1) and EXTERNAL FAULT (TB-13D) circuitry may be disabled if parameters are

reset to factory defaults! The drive must be reprogrammed after a RESET in order to insure

proper operation .

FAILURE TO DO SO MAY RESULT IN DAMAGE TO EQUIPMENT AND/OR INJURY

TO PERSONNEL!

This parameter is used to reset the programmable parameters back to the factory default settings. This

parameter has four possible settings:

MAINTAIN

Maintain parameter settings as they are .

RESET 60

Resets parameters to factory defaults for 60 Hz base frequency.

RESET 50

Resets parameters to factory defaults for 50 Hz base frequency.

RST HIGH

Resets parameters to factory defaults for 650 Hz base frequency. This option will only

appear if the drive is equipped with the High Frequency Output option.

When a factory reset is performed, the following terminals are affected:

TB-1 will be disabled because Parameter 30 - CONTROL will default to LOCAL .

TB-13A, 13B, and 13C will be disabled because Parameters 47, 48, and 49 will default to NONE . If

TB-13C was set to RUN REVERSE, TB-12A will default to a momentary START contact .

TB-13D will default to a normally open EXTERNAL FAULT contact because Parameter 50 - TB13D EXT

will be reset to FAULT .

NOTE:

This parameter will display RESET 60, RESET 50 or RST HIGH until a change is made to one

or more of the parameter settings . Once a parameter is changed, the display will change to MAINTAIN .

66 HISTORY

(CLEAR FAULT HISTORY)

This parameter is used to clear the previous faults in the FAULT HISTORY . When set to CLEAR and the

ENTER key is pushed, the display will change to MAINTAIN, and the FAULT HISTORY will display

NO FAULT for each of the eight fault histories .

69 LANGUAGE

(LANGUAGE SELECTION)

The MICRO Series drive can support other languages with the addition of an optional LANGUAGE

EEPROM chip installed in socket U11 on the control board of the drive. IF the EEPROM is not present,

the default language will be ENGLISH . Also, this parameter is not affected when the parameters are reset

using Parameter 65 - PROGRAM . Therefore, if a language other than ENGLISH is selected, it will remain

in effect after a RESET .