1-4 SPEED #1-#4

(PRESET SPEEDS #1, #2, #3, AND #4)

PRESET SPEEDS are only active when the drive is in AUTO mode, and are activated via contact closures

between terminal TB-2 and terminals TB-13A, TB-13B, and TB-13C . These terminals must be

programmed as preset speed selects using Parameters 47 - 49: TB13A, TB13B, and TB13C .

The preset speeds can only be set to values that are within the operating range defined by the minimum and

maximum frequency (see Parameters: 10 - MIN FREQ, and 11 - MAX FREQ).

The following table shows how each preset speed is selected using the TB-13 terminals . The terms OPEN

and CLOSED refer to the state of the TB-13 terminal relative to TB-2 .

NOTE:

SPEED #4 is selected if any two of the three TB-13 terminals are closed to TB-2

5,6 SKIP #1 & #2

(SKIP SPEED #1 & #2)

7 BAND WID

(SKIP BANDWIDTH)

These parameters are used to prevent the drive from operating continuously at critical speeds, or

frequencies, that cause excessive mechanical vibration of the driven equipment. The SKIP SPEEDS

(Parameters 5 and 6) and the SKIP BANDWIDTH (Parameter 7) are used to define up to two speed

avoidance ranges . The SKIP SPEED settings define the starting point of the speed range that is to be

avoided, and the SKIP BANDWIDTH setting defines how far the speed range extends beyond SKIP

SPEED .

52

PRESET SPEED ACTIVATION

SPEED

# TB-13A

TB13B

TB-13C

1

CLOSED

OPEN

OPEN

2

OPEN

CLOSED

OPEN

3

OPEN

OPEN

CLOSED

4

CLOSED

CLOSED

OPEN

CLOSED

OPEN

CLOSED

OPEN

CLOSED

CLOSED