LEESON Micro Series Compact Inverters User Manual
Page 69

47
TB13A
(TB-13A INPUT FUNCTION)
This parameter is used to select the function of terminal TB-13A . Closing TB-13A to TB-2 activates the
TB-13A input function .
The following functions can be selected:
NONE
Disables the TB-13A function .
0-10VDC
Selects 0-10 VDC as the AUTO speed reference input . The 0-10 VDC signal is
wired to TB-5A and TB-2 .
4-20 MA
Selects 4-20 mA as the AUTO speed reference input . The 4-20 mA signal is wired to
TB-5B and TB-2 .
SPEED#1
Selects PRESET SPEED #1 as the AUTO speed reference .
LOC SEL
Selects LOCAL mode when Parameter 30 - CONTROL is set to BOTH . Drive is in
REMOTE mode if contact closure is not made .
DEC FREQ
Decrease frequency set point. Used with the MOP (motor operated pot) function.
Refer to Section 14 .2 .6 - SPEED REFERENCE SELECTION .
48
TB13B
(TB-13B INPUT FUNCTION)
When operating in JOG mode, the STOP key WILL NOT stop the drive. To stop the drive,
the contact between TB-13B and TB-2 must be opened .
This parameter is used to select the function of terminal TB-13B . Closing TB-13B to TB-2 activates the
TB-13B function . The following functions can be selected:
NONE
Disables the TB-13B function .
0-10VDC
Selects 0-10 VDC as the AUTO speed reference input . The0-10 VDC signal is wired
to TB-5A and TB-2 .
4-20 MA
Selects 4-20 mA as the AUTO speed reference input . The 4-20 mA signal is wired to
TB-5B and TB-2 .
SPEED#2
Selects PRESET SPEED #2 as the AUTO speed reference .
INC FREQ
Increase frequency set point. Used with the MOP (motor operated pot) function. Refer
to Section 14 .2 .6 - SPEED REFERENCE SELECTION .
JOG FWD
Jog in the forward direction. Active only when drive is STOPPED. The jog speed is
set by Parameter 2 -SPEED#2 .
JOG REV
Jog in the reverse direction. Active only when drive is STOPPED. The jog speed is
set by Parameter 2 - SPEED#2 .
67