47

TB13A

(TB-13A INPUT FUNCTION)

This parameter is used to select the function of terminal TB-13A . Closing TB-13A to TB-2 activates the

TB-13A input function .

The following functions can be selected:

NONE

Disables the TB-13A function .

0-10VDC

Selects 0-10 VDC as the AUTO speed reference input . The 0-10 VDC signal is

wired to TB-5A and TB-2 .

4-20 MA

Selects 4-20 mA as the AUTO speed reference input . The 4-20 mA signal is wired to

TB-5B and TB-2 .

SPEED#1

Selects PRESET SPEED #1 as the AUTO speed reference .

LOC SEL

Selects LOCAL mode when Parameter 30 - CONTROL is set to BOTH . Drive is in

REMOTE mode if contact closure is not made .

DEC FREQ

Decrease frequency set point. Used with the MOP (motor operated pot) function.

Refer to Section 14 .2 .6 - SPEED REFERENCE SELECTION .

48

TB13B

(TB-13B INPUT FUNCTION)

When operating in JOG mode, the STOP key WILL NOT stop the drive. To stop the drive,

the contact between TB-13B and TB-2 must be opened .

This parameter is used to select the function of terminal TB-13B . Closing TB-13B to TB-2 activates the

TB-13B function . The following functions can be selected:

NONE

Disables the TB-13B function .

0-10VDC

Selects 0-10 VDC as the AUTO speed reference input . The0-10 VDC signal is wired

to TB-5A and TB-2 .

4-20 MA

Selects 4-20 mA as the AUTO speed reference input . The 4-20 mA signal is wired to

TB-5B and TB-2 .

SPEED#2

Selects PRESET SPEED #2 as the AUTO speed reference .

INC FREQ

Increase frequency set point. Used with the MOP (motor operated pot) function. Refer

to Section 14 .2 .6 - SPEED REFERENCE SELECTION .

JOG FWD

Jog in the forward direction. Active only when drive is STOPPED. The jog speed is

set by Parameter 2 -SPEED#2 .

JOG REV

Jog in the reverse direction. Active only when drive is STOPPED. The jog speed is

set by Parameter 2 - SPEED#2 .

67