49 TB13C
(TB-13C INPUT FUNCTION)
If TB-13C is programmed for RUN REVERSE, TB-1 is disabled and CANNOT be used as a
STOP switch! This is true in LOCAL and REMOTE mode. Incorrect use of TB-1 may result
in damage to equipment and/or injury to personnel!
This parameter is used to select the function of terminal TB-13C . Closing TB- 13C to TB-2 activates the
TB-13C input function . The following functions can be selected .
NONE
Disables the TB-13C function .
0-10VDC
Selects 0-10 VDC as the AUTO speed reference input . The 0-10 VDC signal is wired
to TB-5A and TB-2 .
4-20 MA
Selects 4-20 mA as the AUTO speed reference input . The 4-20 mA signal is wired to
TB-5B and TB-2 .
SPEED#3
Selects PRESET SPEED #3 as the AUTO speed reference .
LOC SEL
LOCAL SELECT - Selects LOCAL mode when Parameter 30 - CONTROL is set to
BOTH . Drive is in REMOTE mode if contact closure is not made .
RUN REV
RUN REVERSE - Run in reverse direction. Requires a maintained contact closure -
close to RUN in reverse direction, open to STOP . This will cause TB-12A to function
as RUN FORWARD, also requiring a maintained contact.
STRT REV
START REVERSE - Start in reverse direction. Requires a momentary contact closure
to RUN in reverse direction . A momentary STOP contact must be wired between
TB-1 and TB-2 . Setting this parameter to START REVERSE causes TB-12A to
function as START FORWARD, also requiring a momentary contact closure to RUN
in forward direction .