49 TB13C

(TB-13C INPUT FUNCTION)

If TB-13C is programmed for RUN REVERSE, TB-1 is disabled and CANNOT be used as a

STOP switch! This is true in LOCAL and REMOTE mode. Incorrect use of TB-1 may result

in damage to equipment and/or injury to personnel!

This parameter is used to select the function of terminal TB-13C . Closing TB- 13C to TB-2 activates the

TB-13C input function . The following functions can be selected .

NONE

Disables the TB-13C function .

0-10VDC

Selects 0-10 VDC as the AUTO speed reference input . The 0-10 VDC signal is wired

to TB-5A and TB-2 .

4-20 MA

Selects 4-20 mA as the AUTO speed reference input . The 4-20 mA signal is wired to

TB-5B and TB-2 .

SPEED#3

Selects PRESET SPEED #3 as the AUTO speed reference .

LOC SEL

LOCAL SELECT - Selects LOCAL mode when Parameter 30 - CONTROL is set to

BOTH . Drive is in REMOTE mode if contact closure is not made .

RUN REV

RUN REVERSE - Run in reverse direction. Requires a maintained contact closure -

close to RUN in reverse direction, open to STOP . This will cause TB-12A to function

as RUN FORWARD, also requiring a maintained contact.

STRT REV

START REVERSE - Start in reverse direction. Requires a momentary contact closure

to RUN in reverse direction . A momentary STOP contact must be wired between

TB-1 and TB-2 . Setting this parameter to START REVERSE causes TB-12A to

function as START FORWARD, also requiring a momentary contact closure to RUN

in forward direction .

68