Example:

The critical frequency is 21 Hz, and a bandwidth of 2 Hz is desired. Therefore, set SKIP #1 to 20

Hz and set SKIP BANDWIDTH to 2 Hz. This results in a speed range from 20 Hz to 22 Hz that the drive

will not operate within continuously. If the drive were operating at 25 Hz and then commanded to operate

at a speed within the range of avoidance, the drive would decelerate to 22 Hz and remain at that frequency

until commanded to 20 Hz or below. The drive would then decelerate through the range of avoidance to

the new frequency. Likewise, if the drive were operating at 18 Hz, and then commanded to operate at a

speed within the range of avoidance, the drive would accelerate to 20 Hz and remain at that frequency until

commanded to a speed of 22 Hz or above. The drive would then accelerate through the range of avoidance

to the new frequency.

8 ACCEL

(ACCELERATION TIME)

ACCEL sets the acceleration rate for all speed reference sources (keypad, speed pot, 4-20 mA, 0-10

VDC, jog, and the preset speeds). The ACCEL setting is the time to accelerate from 0 Hz to the BASE

FREQUENCY (Parameter 18). The range of adjustment for ACCEL depends on horsepower. Refer to the

table below:

Example:

If ACCEL is set to 30 seconds, and the BASE FREQUENCY is set for 60 Hz, the drive will ramp

from 0 Hz to 60 Hz in 30 seconds. This is a linear function, therefore the drive would ramp up to 30 Hz

in 15 seconds, etc .

NOTE:

The ability to accelerate a given load at a particular rate will be limited by the output power

capability of the drive/motor combination . The acceleration of high-inertia and high-friction loads may

be affected by the current limiting characteristics of the drive . See Parameters: 16 - CURRENT, 19 - FX

BOOST, and 20 - AC BOOST for more information .

9 DECEL

(DECELERATION TIME)

This parameter sets the deceleration rate for all speed reference sources . The DECEL setting indicates time

to decelerate from BASE FREQUENCY to 0 Hz. As with Parameter 8 - ACCEL, this is a linear function.

If the drive is set to COAST to stop, this parameter will have no effect when a STOP command is given .

The range of adjustment for DECEL depends on the horsepower and voltage rating, and whether Dynamic

Braking is being used. Refer to the table on next page:

53

ACCELERATION LIMITS

120 - 240 Vac

400 - 590 Vac

RANGE OF

MODELS

MODELS

ADJUSTMENT

0 .25 - 20 HP

1 - 20 HP

0 .1 - 3600 SEC

25 - 30 HP

25 - 60 HP

0 .3 - 3600 SEC

75 - 150 HP

1 .0 - 3600 SEC