LEESON Micro Series Compact Inverters User Manual

Page 81

Advertising
background image

each type, so the same type of signal cannot be used for transducer feedback and set point reference. For

example, a 4-20 mA signal from a transducer could not be used as a feedback signal if the set point is being

controlled by a 4-20 mA signal from a PLC .

19.5 TUNING THE PID CONTROL

Once the PID control is set up correctly, it needs to be tuned in order to maintain the process set point .

First, set the Integral and Differential Gains to zero, and increase the Proportional Gain (Parameter 77)

until the system becomes unstable, then lower the gain until the system stabilizes again. Set the Proportional

Gain about 15% less than that value that stabilizes the system. If only Proportional Gain is used, and the

system is operating in a steady-state condition (set point is fixed and process variable has settled to a fixed

value), there will always be a certain amount of error in the system. This is called the steady-state error.

Integral Gain (Parameter 78) is used to force the steady-state error to zero by increasing the output speed

command with respect to time. Over time, the error will be forced to zero because the Integral term will

continue to change the speed command, even after the Proportional term reaches steady state and no longer

affects the speed command . The Integral Gain affects the rate of rise of the output speed command from

the Integral term . Small amounts of Integral Gain can cause large changes in PID performance, so care must

be taken when adjusting Integral Gain. Too much Integral Gain will result in overshoots, especially if large

step changes in error occur .

Typically, Proportional and Integral Gain are all that is needed to fine-tune the system . However, it may

be necessary to use Differential Gain (Parameter 79) to further stabilize the system, especially when quick

responses are required. The Differential term responds to the rate of change of the error, not the actual error

itself. Differential Gain acts like a “shock-absorber” to dampen overshoots that can occur when the PID

tries to react quickly to changes in error or set point. This allows fast PID response, with reduced risk of

becoming unstable due to overshoots . The Differential term is very sensitive to electrical noise on the

feedback signal and to digitizing errors, so it must be used with caution.

The other parameter setting that affects the response of the PID control is Parameter 80 - PID ACC . This

sets the acceleration (and deceleration) rate of the set point reference into the PID unit. When the set point

changes, this function will “filter” the input to the PID unit by ramping the set point reference from the

previous value to the new value . This will help prevent overshoots that can occur when the PID control

attempts to respond to step changes in set point, resulting in smoother operation . If PID ACC is set to 0 .0

seconds, it is effectively disabled .

19.6 MICRO SERIES DISPLAY IN PID MODE

79

Advertising