11.0 MICRO SERIES POWER WIRING DIAGRAM

Do not connect incoming AC power to output terminals T1, T2, or T3 . Severe damage to the

drive will result .

INSTALL, WIRE, AND GROUND IN ACCORDANCE WITH ALL APPLICABLE CODES .

NOTES:

1 . Wire the motor for the proper voltage per the output rating of the drive . Motor wires MUST be run

in a separate steel conduit away from control wiring and incoming AC power wiring .

2 . Do not install contactors between the drive and the motor without consulting LEESON for more

information . Failure to do so may result in drive damage .

3. Remove any existing, and do not install, power factor correction capacitors between the drive and the

motor . Failure to do so will result in drive damage .

4 . Use only UL and CSA listed and approved wire .

5 . Minimum wire voltage ratings: 300 V for 120, 200 and 240 VAC systems, and 600 V for 400, 480,

and 590 VAC systems .

6 . Wire gauge must be based on a minimum of 150% of the rated output current of the drive, and a

minimum 75 C insulation rating . Use copper wire only .

7 . Wire and ground in accordance with NEC or CEC, and all applicable local codes .