6.2.3 MICRO SERIES INPUTS AND OUTPUTS
The drive has two analog inputs (0-10 VDC and 4-20 mA) that can be used for speed reference, PID
set point reference, or PID feedback. A speed potentiometer (10,000 Ohm) can be used with the 0-10
VDC input .
There are also two analog outputs: one is proportional to speed (frequency), and the other is proportional
to load .
The drive has three programmable outputs for status indication: one Form C relay and two open-collector
outputs .
Refer to Sections 14 .0 - CONTROL WIRING and 15 .0 - CONTROL WIRING DIAGRAMS for more
information .