LEESON Micro Series Compact Inverters User Manual
Page 44

15.3
THREE-WIRE START/STOP CONTROL
Shown below is the wiring diagram for a typical three-wire start/stop control scheme, using momentary
contacts (such as push buttons) for START and STOP commands. Also shown is the wiring for a 0-10 VDC
or 4-20 mA speed reference signal .
NOTES:
1 . Momentarily close TB-12A to TB-2 to START, and momentarily open TB- 1 to TB-2 to STOP .
2. If REVERSE direction is required, ROTATION must be set to FWD&REV, and TB-13C must be
set to START REVERSE (refer to Parameters: 27 - ROTATION, and 49 - TB13C).
If REVERSE is not required, wire the Start button directly to TB-12A and eliminate the
FWD/REV switch.
3 . Program TB-13A, 13B, or 13C to select the appropriate speed reference signal that will control the
drive speed (refer to Parameters 47, 48, and 49). When that TB-13 terminal is closed to TB-2, the
drive will respond to the selected speed reference signal . In the diagram above, TB-13A is programmed
to select either a 0-10 VDC or 4-20 mA signal .
4 . If the contact closure is not made between TB-13A and TB-2 to select a speed reference, the drive will
default to MANUAL speed control, which is determined by Parameter 29 - MANUAL .
42