18.0 DESCRIPTION OF PARAMETERS

0

LINE VOLTS

(LINE VOLTAGE)

This parameter calibrates the drive for the correct input voltage, and can be set to AUTO, HIGH, or LOW .

When set to AUTO, the drive measures the DC bus voltage when power is applied and automatically

calibrates itself according to the measured value (DC bus voltage is equal to input voltage multiplied by 1.4).

This parameter can also be set “manually”, using the HIGH or LOW settings. For actual line voltages

of 230/240 Vac (on 240/200 Vac models), 460/480 Vac (on 480/400 Vac models), or 575/590 Vac (on

590/480 Vac models), set this parameter to HIGH. Also use the HIGH setting for 240/120 Vac single phase

input models . Refer to the table below .

For actual line voltages of 200/208 Vac (on 240/200 Vac models), 380/415 Vac (on 480/400 Vac models),

or 460/480 Vac (on 590 Vac models), set this parameter to LOW. Refer to the table below.

INPUT LINE VOLTAGE SELECTION

RATED

INPUT

ACTUAL

PARAMETER

INPUT VOLTAGE

PHASE

LINE VOLTAGE

SETTING

240/120 VAC

1

230/240 VAC

HIGH

240/120 VAC

1

115/120 VAC

HIGH

240 VAC

1

230/240 VAC

HIGH

240/200 VAC

3

230/240 VAC

HIGH

240/200 VAC

3

200/208 VAC

LOW

480/400 VAC

3

460/480 VAC

HIGH

480/400 VAC

3

380/415 VAC

LOW

590/480 VAC

3

575/590 VAC

HIGH

590/480 VAC

3

460/480 VAC

LOW