20.0 TROUBLESHOOTING

The table below lists the fault conditions that will cause the drive to shut down, as well as some possible

causes . Please contact the factory for more information on troubleshooting faults .

NOTE: The drive will not automatically restart after a PWR SAG or a CONTROL fault. Also, if an
OUTPUT fault occurs below 1.5 Hz, the drive will only attempt one restart, after a four minute delay.
If unsuccessful, it will then trip into FAULT LOCKOUT, which will require a manual reset. This is
done to protect the drive in case of a shorted motor.

NOTE 2: In the event of an OVERLOAD fault there is a 3 minute delay before resetting is pos-
sible. This is a requirement of UL508C. The delay is intended to allow time for the motor to cool. If
power is removed when the drive is in an OVERLOAD fault state, then when power is restored the
OVERLOAD fault will still be present and the delay will still be active even is power was removed for
longer than 3 minutes.

FAULT MESSAGES

FAULT

DESCRIPTION

POSSIBLE CAUSES

OUTPUT

Output transistor fault: Output current

Phase to ground short .

exceeded 200% of drive rating.

Phase to phase short.

FX or AC BOOST set too high .

Bad transistor module (IPM).

LO VOLTS

Low DC Bus Voltage fault: DC

Low line voltage .

bus voltage below 60% of normal .

HI VOLTS

High DC Bus Voltage fault: DC bus

High line voltage .

voltage above 120% of normal .

Overhauling load .

DECEL rate is set too fast .

HI TEMP

Temperature fault: Internal drive

Ambient temperature too high .

temperature too high.

Fan failure (if equipped).

OVERLOAD

Current Overload fault: Output

Drive undersized for the

current rating exceeded for too long.

application.

Problem with the motor

and/or the driven equipment.

PWR TRAN

Power Transient fault: Low line

AC line dipped or sagged .

voltage .

PWR SAG

Power Sag fault ; Control board voltage

Erratic AC line .

below tolerance .

A new control board has been installed

Perform a factory reset using

that is different from the previous

Parameter 65-PROGRAM .

version .

This will update the software

and allow the fault to be reset .

LANGUAGE

Language fault: Selected language

Defective language EEPROM .

not present.

Language EEPROM (U11)

removed after programming .