20.0 TROUBLESHOOTING
The table below lists the fault conditions that will cause the drive to shut down, as well as some possible
causes . Please contact the factory for more information on troubleshooting faults .
NOTE: The drive will not automatically restart after a PWR SAG or a CONTROL fault. Also, if an
OUTPUT fault occurs below 1.5 Hz, the drive will only attempt one restart, after a four minute delay.
If unsuccessful, it will then trip into FAULT LOCKOUT, which will require a manual reset. This is
done to protect the drive in case of a shorted motor.
NOTE 2: In the event of an OVERLOAD fault there is a 3 minute delay before resetting is pos-
sible. This is a requirement of UL508C. The delay is intended to allow time for the motor to cool. If
power is removed when the drive is in an OVERLOAD fault state, then when power is restored the
OVERLOAD fault will still be present and the delay will still be active even is power was removed for
longer than 3 minutes.
FAULT MESSAGES
FAULT
DESCRIPTION
POSSIBLE CAUSES
OUTPUT
Output transistor fault: Output current
Phase to ground short .
exceeded 200% of drive rating.
Phase to phase short.
FX or AC BOOST set too high .
Bad transistor module (IPM).
LO VOLTS
Low DC Bus Voltage fault: DC
Low line voltage .
bus voltage below 60% of normal .
HI VOLTS
High DC Bus Voltage fault: DC bus
High line voltage .
voltage above 120% of normal .
Overhauling load .
DECEL rate is set too fast .
HI TEMP
Temperature fault: Internal drive
Ambient temperature too high .
temperature too high.
Fan failure (if equipped).
OVERLOAD
Current Overload fault: Output
Drive undersized for the
current rating exceeded for too long.
application.
Problem with the motor
and/or the driven equipment.
PWR TRAN
Power Transient fault: Low line
AC line dipped or sagged .
voltage .
PWR SAG
Power Sag fault ; Control board voltage
Erratic AC line .
below tolerance .
A new control board has been installed
Perform a factory reset using
that is different from the previous
Parameter 65-PROGRAM .
version .
This will update the software
and allow the fault to be reset .
LANGUAGE
Language fault: Selected language
Defective language EEPROM .
not present.
Language EEPROM (U11)
removed after programming .