4 natural gas setup, Natural gas setup -7 – Yokogawa EJX930A User Manual

Page 100

Advertising
background image

<7. Operation of EJXMVTool>

7-7

IM 01C25R51-01E

7.1.4 Natural Gas Setup

(1) AGA8 Detail Characterization Method

Figure 7.4

Natural Gas Setup Screen (1)

Input the value as mole percent for each component shown in Table 7.6.

The each value must be specified with in the range shown in Table 7.6.

Total mole percent must become 100%.

• Standardize: Standardize the mole component value.

Click [Standardize] button when total mol percent does not become 100%.

• Reset: Reset the mole component value
• Total mole: Total mole percent is displayed

NOTE

In case that “Total Mole” is displayed as “100%”, error message is displayed as follows.

“The total mole should exactly be 100%”

Click [Standardize] button.