<8. Operation of DYFMVTool>

8-20

IM 01C25R51-01E

8.3.1 Case1: Arithmetic Function Block is Standalone

Following is the procedures for confirming flow configuration in case AR Block is standalone.

Step 1 Set function block scheduling information

Set the function block scheduling information to activate digitalYEWFLO AR Block.

Regarding function block scheduling, refer to Appendix B-2.

Step 2 Open Online Parameter in Device DTM

Start Device DTM to display the Online Parameter screen.

([Device] → [Parameter] → [Online Parameter])

IMPORTANT

Turn on the alarm output of AR Block at TB: ALARM_PERFORM.

Default setting for the alarm output of AR Block is off.

([Online Parameter] → [Transducer Block] → [Alerts])

Step 3 Set input conditions in AR Block

Set value to following input parameters (Refer to Figure 8.19 and Table 8.10):

“Input.Value”, “Input1.Value” and “Input2.Value”

([Online Parameter] → [Arithmetic] → [Dynamic Variables])

Table 8.10

Input conditions in AR Block

Input

Device

Function

Block

Parameter

Value

Unit

Volumetric Flow

Rate

digitalYEWFLO

AR Block

(Input Section)

IN

Input.Value

(Relative Index: 14)

<Effective Mode: Auto/MAN/OOS>

Volumetric Flow Unit

(Relative Index: 37)

Temperature

AR Block

(Input Section)

IN_1

Input 1.Value

(Relative Index: 16)

<Effective Mode: Auto/MAN/OOS>

Temperature Unit

(Relative Index: 38)

Pressure

AR Block

(Input Section)

IN_2

Input 2.Value

(Relative Index: 17)

<Effective Mode: Auto/MAN/OOS>

Pressure Unit

(Relative Index: 40)

IMPORTANT

Confirm the settings in "Volumetric Flow Unit", "Temperature Unit", and "Pressure Unit".

Regarding “Temperature Unit”, “Pressure Unit”, refer to section 8.1.1.

([Online Parameter] → [Arithmetic] → [Configuration] → [Density Factor Parameters])

IMPORTANT

Before entering the input parameters, set the Function Block Mode in AR Block by referring to

Table 8.10.