<8. Operation of DYFMVTool>

8-22

IM 01C25R51-01E

8.3.2 Case2: AR Block is Connected with Other Devices

The procedures below are for confirming flow configuration when AR Block is connected with

other devices.

Step 1 Set function block scheduling information

Set the function block scheduling information to activate digitalYEWFLO AR Block and the

connected function block. Regarding function block scheduling, refer to Appendix B-2.

Step 2 Set function block connection information

Connect the function block output to digitalYEWFLO AR Block input. Regarding function block

connection, refer to Appendix B-2.

Step 3 Open Online Parameter in Device DTM

Start Device DTM to display the Online Parameter screen.

([Device] → [Parameter] → [Online Parameter])

IMPORTANT

Turn on the alarm output of AR Block at TB: ALARM_PERFORM.

Default setting for the alarm output of AR Block is off.

([Online Parameter] → [Transducer Block] → [Alerts])

IMPORTANT

Confirm the settings in "Volumetric Flow Unit", "Temperature Unit" and "Pressure Unit".

Regarding "Temperature Unit", "Pressure Unit", refer to section 8.1.1.

([Online Parameter] → [Arithmetic] → [Configuration] → [Density Factor Parameters])

Step 4 Set input conditions in Connected Device’s AI Block

Set the value in the following input parameters (Refer to Figure 8.19 and Table 8.12):

Input the values of volumetric flow rate, temperature, and pressure in Manual mode or

Simulation mode of Connected Device’s AI Block.