<7. Operation of EJXMVTool>

7-19

IM 01C25R51-01E

7.2.2 Basic Mode Setup

Select a Fluid Type from “Gas” or “Liquid”.
(1) Gas (Default)

Figure 7.19 Basic Mode Setup Screen

• Input Reference Temperature (Tb), Reference Static Pressure (SPb), and Kfactor.

NOTE

The static pressure value is according to the transmitter’s abs and gauge selection (A/G select).

But same unit character is used for both absolute and gauge.

The procedure for setting the BASIC Mode is as follows. For details on how to calculate the

Kfactor, refer to the EJX910A and EJX930A Multivariable Transmitters User’s Manual (IM

01C25R01-01E).

Table 7.11

Flow Operational Expression

T0701E.ai

*1:

mark indicate User Input

*2:

Kfactor must be calculated according to the Flow unit category

*3:

Reter to table 7.5, 7.6, 7.7

× ∆P × T/Tb × SPb/SP

Fluid

type

Flow unit

Category

*3

Kfactor

*2

Flow Equation

Mass Flow

Mass Flow

Volume Flow

Volume Flow

Gas

Liquid Normal·Standard

Volume Flow

Normal·Standard

Volume Flow

Kfactor = /4 × Nc × C/ 1−β

4

× ε × d

2

Ч 2 Ч ρb

Ч 2 Ч ρb / ρ norm

× 2 / ρb

Ч 2 Ч ρb × 1/K

Ч 2 Ч ρb × 1/K / ρ norm

× 2/(ρb × 1/K)

Qm or Qv or Qv_norm

= Kfactor

Qm or Qv_norm

= Kfactor

× ∆P × Tb/T × SP/SPb

Qv= Kfactor

Kfactor = /4 × Nc × C/ 1−β

4

× ε × d

2

Kfactor = /4 × Nc × C/ 1−β

4

× ε × d

2

Kfactor = /4 × Nc × C/ 1−β

4

× ε × d

2

Kfactor = /4 × Nc × C/ 1−β

4

× ε × d

2

Kfactor = /4 × Nc × C/ 1−β

4

× ε × d

2

× ∆P × (1+Temp K1 × (T–Tb))

*1

*1

*1