<Appendix B. Device Information>

B-9

IM 01C25R51-01E

Step 3 Check the alarm in AR Block

Confirm that the following alarms are not displayed in Diagnostic List of the Device Status screen.
If any alarm is displayed for AR Block, take the appropriate measure by referring to the table

below.

Table B3.1 Alarm list of AR Block for flow configuration

Alarm No.

Alarm Label

Counter Measure

AL-85

AR Not Scheduled

Make a schedule of AR Block

AL-86

AR Range Conf. Err

Change the value as AR Range High (AR.RANGE_HI) is larger

than AR Range Low (AR.RANGE_LO)

AL-87

AR Temp. IN Over Range

This case is out of specification. Refer to IM01F06F00-01E or

Check the engineering setting or AR Temperature Unit

(AR.AR_TEMPERATURE_UNIT)

AL-88

AR Press IN Over Range

This case is out of specification. Refer to IM01F06F00-01E or

Check the engineering setting or AR Pressure Unit (AR.AR_

PRESSURE_UNIT) and AR Bias Input2 (AR.BIAS_IN_2)

AL-89

AR Flow IN NotConnected

Connect the volumetric flow data into AR Input (AR.IN)

AL-90

AR Temp. IN NotConnected

Connect the temperature data into AR Input1 (AR.IN_1)

AL-91

AR Press IN NotConnected

Connect the pressure data into AR Input2 (AR.IN_2)

AL-92

AR Comp. Coef. Conf. Err

Execute “Flow Configuration Wizard” again and download to the

device.

AL-93

AR Output Unit Conf. Err

Refer to IM 01F06F00-01E or Check the AR Output Range.Units

Index (AR.OUT_RANGE.Unit Index) and AR Arithmetic Type

(AR.ARITH_TYPE)

NOTE

As for device alarms other than AR Block, refer to Instruction Manual "Model DY Vortex

Flowmeter, Model DYA Vortex Flow Converter, and Fieldbus Communication Type" (IM

01F06F00-01E).