B-3 How to Check digitalYEWFLO AR Block

Alarm

Confirm AR Block functions correctly by following the procedures below.

Step 1 Open Online Parameter in Device DTM

Start Device DTM to display the Online Parameter screen.
([Device] → [Parameter] → [Online Parameter])

IMPORTANT

Turn on the alarm output of AR Block at TB: ALARM_PERFORM.

Default setting for the alarm output of AR Block is off.

(Online Parameter: [Transducer Block] → [Alerts])

Step 2 Open the Device Status screen

Display the alarm of AR Block in Diagnostic List of the Device Status screen.
([Online Parameter] → [Device Status] → [Diagnostic List])

NOTE

The alarm information on AR Block appears under “Others” of Diagnostic List.

Figure B3.1 Device Status screen