<7. Operation of EJXMVTool>

7-13

IM 01C25R51-01E

(2) Gas or Steam (Category: Saturated steam)

Figure 7.11 Fluid Operating Range Setup Screen (2)

Input operating range and select units
Pressure unit is selectable from kPa abs, bar abs, psi abs, kPa gauge, bar gauge, psi gauge
Atmospheric Pressure unit is selectable from: psi abs, bar abs, kPa abs

Input reference condition and select units
Pressure unit is selectable from kPa abs, bar abs, psi abs

NOTE

• After clicking the [Next] button, if a “The specified operating condition includes both gas

and liquid phases.” information message is displayed, the operating condition is near the

acceptable limits for liquid and gas.

Figure 7.12 Warning message

• Please confirm the density value on the following page (fluid physical property setup page)

and continue configuration.

• If the pressure range input on the Fluid Operating Range Setup is too wide, there is a

probability of the calculation error of density is big.

• These ranges are used only for the density and viscosity calculation.

• Ranges of Transmitter are not changed.