<8. Operation of DYFMVTool>

8-21

IM 01C25R51-01E

IMPORTANT

Before inputting values, set "Good_NonCascade::NonSpecific:NotLimited" status in the following

parameters:

“Input.Status”, “Input1.Status” and “Input2.Status”

([Online Parameter] → [Arithmetic] → [Configuration] → [Input Parameters])

*: To show "Good_NonCascade::NonSpecific:NotLimited", open the pull-down menu of each

Status parameter and press the [G] key.

Step 4 Confirm output in AR Block

Confirm the value of the following output parameters (Refer to Figure 8.19 and Table 8.11):

“Density Factor.Value” and ”Pre Output.Value”.

([Online Parameter] → [Arithmetic] → [Dynamic Variables])

Table 8.11

Output in AR Block

Output

Device

Function Block

Parameter

Value

Unit

Density

digitalYEWFLO

AR Block

(Computing Section)

DENSITY_FACTOR

Density Factor.Value

(Relative Index: 48)

<Effective Mode: Auto/MAN/OOS>

Density Factor Unit

(Relative Index: 49)

Mass Flow

Rate

AR Block

(Output Section)

PRE_OUT

Pre Output.Value

(Relative Index: 9)

<Effective Mode: Auto/MAN/OOS>

Output Range.Units

Index

(Relative Index: 11)

IMPORTANT

Make sure that no alarming status of AR Block is shown in Device Status, and then confirm the

value of output parameters. Refer to Appendix B-3 for alarm.

([Online Parameter] → [Device Status] → [Diagnostic List])

IMPORTANT

Make sure "Good_NonCascade::NonSpecific:NotLimited" status of the following parameters

before confirming the values:

“Density Factor.Status” and “Pre Output.Status”

([Online Parameter] → [Arithmetic] → [Dynamic Variables])

NOTE

Confirm the settings in "Density Factor Unit" and "Output Range.Unit Index".

([Online Parameter] → [Arithmetic] → [Configuration] → [Density Factor Parameters])

([Online Parameter] → [Arithmetic] → [Configuration] → [Output Parameters])