<8. Operation of DYFMVTool>

8-19

IM 01C25R51-01E

8.3 How to Confirm Flow Configuration

After performing flow configuration for the device by using "Flow Configuration Wizard" and

"Download to Device", execute the following procedures to confirm the configuration.

NOTE

Regarding start up procedure of digitalYEWFLO and DYFMVTool, refer to Appendix B-1.

IMPORTANT

Use function block scheduling and connection tool for DYFMVTool. After using these setting tool,

finish the program before starting FlowNavigator.

The procedures differ depending on whether AR Block is used standalone or connected with

other devices.

Case1: AR Block is standalone. Refer to section 8.3.1
Case2: AR Block is connected with other devices. Refer to section 8.3.2

Figure 8.19 shows the parameters for confirming the flow configuration.
Regarding Flow Calculation of digitalYEWFLO and DYFMVTool, refer to section 6.1.3 and

the document "Model DY Vortex Flowmeter, Model DYA Vortex Flow Converter, Fieldbus

Communication Type" (IM 01F06F00-01E).

RANGE_HI

PV

t_1

RANGE_LO

func

ARITH_TYPE

RANGE

EXTENSION

FUNCTION

Input Section

Computing Section

ARITH_TYPE

32 to 38

COMP_LO_LIM

COMP_HI_LIM

Output Section

x GAIN

+ BIAS

MAN

O/S

OUT_LO_LIM

OUT_HI_LIM

ARITH_TYPE

1 to 10

Main input

unit conversion

(User unit -> m3/s)

Compensation

Calculation

Connection

check

Device Flow Parameter

Compensation

limitation

Mass Flow Rate

(PV' x CF)

COMP_LO_LIM

COMP_HI_LIM

Output Flow Rate

unit conversion

(kg/s -> User unit)

OUT_RANGE.Units Index

F0819E.ai

PV

t_1

VOLUMETRIC_FLOW_UNIT

Mass Flow Rate /

func

Volumetric Flow Rate at

Normal Condition

PVí

CF

PV: Volumetric Flow Rate

t_1: Temperature

t_2: Pressure

CF: Compensation Factor

BIAS_IN_1,2 GAIN_IN_1,2

(IN_1+BIAS_IN_1) x GAIN_IN_1

(IN_2+BIAS_IN_2) x GAIN_IN_2

t_2

t_2

AI3-Volumetric

Flow Rate (Qv)

digitalYEWFLO

AR Block

Case1

Case2

Built-in Temperature Sensor
AI2-Temperature

Pressure Transmitter

AI-Pressure

Temperature Transmitter

AI-Temperature

IN_2

OUT

SIMULATE

OUT

SIMULATE

OUT

SIMULATE

OUT

SIMULATE

OUT

PRE_OUT

DENSITY_FACTOR.Value

IN_1

IN

Set input condition in

Connected Device's AI Block

Confirm input condition in AR Block

Confirm output in AR Block

Confirm output in AR Block

Set input condition in AR Block

Figure 8.19 Parameters for flow configuration confirmation