Operational flowchart – Yokogawa EJX930A User Manual

Page 66

Advertising
background image

<5. Operational Flowchart>

5-4

IM 01C25R51-01E

(C) Configure with existing Configuration File (XMV file)

Step

FieldMate Menu

EJX910 HART/F

OUNDATION

fieldbus DTM

Layer1

Layer2

Layer3

EJXMVTool

Main Window

Description

"Online Parameter" is opened.
Upload "Device Flow Parameters"

and "Device General Parameters".

Edit "Device General Parameters"

and Apply "Offline Database".

"Import -> Import XMV Menu"

Import "User Flow Parameters"

and "Device Flow Parameters"

from existing file (*.xmv file).

Confirm / Modify compensation

mode.

Confirm / Modify "User Flow

Parameters".

Confirm / Modify "User Flow

Parameters".

Confirm / Modify "User Flow

Parameters".

Confirm / Modify "User Flow

Parameters" and "Device Flow

Parameters".

"Export -> Export XMV Menu"

Export "User Flow Parameters"

and "Device Flow Parameters" to

binary file.

Download

"Device Flow Parameters" and

"Device General Parameters".

Check the flow coefficient.

The value is saved in a log file.:

"FlowCoeffLog"

"Report Menu"

Export "User Flow Parameters" in

CSV file format.

Apply "Device Flow Parameters"

to "Offline Database".

Goes offline.

1

Start DTM and

upload

parameter

from the

device

Import

existing

file and

confirm /

modify flow

configuration

Download

parameter to

the device

Confirm flow

coefficient

2

3

4

Device

Device

Parameter

Offline

Parameter

Flow

Configuration

Wizard

Flow

Configuration

Mode

Primary

Device and

Pipe Setup

Fluid Type

Setup

Fluid

Operating

Range Setup

Fluid Physical

Property

Setup

Apply Flow

Configuration

Assigned DTM

Device

Download to

device 2)

Upload from

device 1)

Additional

Functions

Additional

Functions

Obtain Flow

Coefficient

Disconnect

Device

F0503E.ai

1)

Before starting operation, execute ‘Upload from device’, so that the “Device General Parameters” in the offline

database are synchronized with the device.

Upload data from the device does not include “User Flow Parameters”.*

*: “User Flow Parameters” consist of primary device information, fluid information and operating condition.

2)

Executing ‘Download to device’ will write both “Device Flow Parameters” and “Device General Parameters” into

the device. Before executing ‘Download to device’, execute ‘Upload from device’, so as to make “Device General

Parameters” in the offline database synchronized with the device.

Download data to device does not include “User Flow Parameters”.

Advertising
This manual is related to the following products: