Important – Yokogawa EJX930A User Manual

Page 73

Advertising
background image

<5. Operational Flowchart>

5-11

IM 01C25R51-01E

Step 3 Download to Device

Perform “Download to Device”. “Device Flow Parameters” will then be downloaded together with

the “Device General Parameters” to the device.

IMPORTANT

For F

OUNDATION

Fieldbus, following block must be checked on the “Download blocks” menu in

the Offline Parameter screen to download “Device Flow Parameters” set by Flow Configuration

Wizard.

EJX910 F

OUNDATION

fieldbus DTM: FTB block

DYF(SoftDL) F

OUNDATION

fieldbus DTM: AR block

“Download blocks” menu
(EJX910 F

OUNDATION

fieldbus DTM)

“Download blocks” menu
(DYF(SoftDL) F

OUNDATION

fieldbus DTM)

F0508E.ai

Figure 5.1 “Download blocks” menu in the Offline Parameter

Offline Parameter

Flow Configuration Wizard

Offline Parameter

Offline

Database

Offline

Database

Offline

Database

Step 1

Step 2

Step 3

Device General Parameters (Default value: , Configured value: )
Device Flow Parameters (Default value: , Configured value: )

*: Confirm the checkbox on the “Download blocks” menu in the Offline Parameter (refer to Figure 5.1)

*

F0509E.ai

Figure 5.2

Procedure to Download the Parameters to the Device

Advertising