B-2 how to configure digitalyewflo ar block – Yokogawa EJX930A User Manual

Page 149

Advertising
background image

<Appendix B. Device Information>

B-2

IM 01C25R51-01E

B-2 How to Configure digitalYEWFLO AR Block

This section explains how to set the function block scheduling and connection information with

the following device as an example.
In this example, NI-FBUS Configurator 3.1 is used as a setting tool.

Table B2.1 Object device (Case 1: AR Block is standalone)

Value

Device

Function

Block

Input to

AR Block

Output from

AR Block

Factory setting

of scheduling

information

(1) Mass Flow Rate

digitalYEWFLO

AR Block

Table B2.2 Object device (Case 2: AR Block is connected with other devices)

Value

Device

Function

Block

Input to

AR Block

Output from

AR Block

Factory setting

of scheduling

information

(1) Volumetric Flow Rate

(Qv)

digitalYEWFLO

AI3 Block

(2) Temperature

Temperature Transmitter

(Yokogawa YTA320)

AI1 Block

(3) Pressure

Pressure Transmitter

(Yokogawa EJX510A)

AI1 Block

(4) Mass Flow Rate

digitalYEWFLO

AR Block

Step 1 Confirm the installation status of the device DD.

To set the device by using NI-FBUS Configurator, the device DD must be successfully installed in

the following folder.
“<WinInstDrive>:\Program Files\National Instruments\NI-FBUS\Data\594543”
(<WinInstDrive>: Windows installed drive)

(The folder name “594543” indicates that the manufacturer is Yokogawa Electric Corporation.)

The DD files are saved for each model in the folder. Confirm that the latest DD files (FileName:

AABB.ffo, AABB.sym*) are installed for each device.
(*: AA = “Device Revision”, BB = “DD Revision”, For example: 0301.ffo and 0301.sym)

• digitalYEWFLO: Folder name “0009”
• YTA320: Folder name “0005”
• EJX510A: Folder name “000C”