If data collection is enabled for input location data (Inlocs) on the

CR10X-TD/PB family dataloggers or Public tables on CR1000, CR3000,

CR800, CR5000 or CR9000 dataloggers, the current values will be collected

every time a scheduled collection occurs, whether or not the values have been

updated. Therefore if your scan interval were one minute in the datalogger

program, and the data collection interval were 30 seconds, you would get two

identical records in the Public table for each one minute scan.

4.2.5.2.3 Communications Path Considerations

When setting up data collection intervals for the dataloggers you should

consider the communications path to the datalogger, and its affect on how often

you can retrieve data.

Phone modems require anywhere from 10 – 30 seconds or more to establish

communication, negotiate baud rate, and start transferring data. Therefore, it is

not a good idea to schedule collection by phone modem more often than once

every two minutes. The time to make a call and start communications should

be considered when you are collecting from multiple stations by phone.

Sufficient time should be allowed for the server to dial the station, retrieve the

data, and then contact the next station. There should be enough time between

calls to the first station that the calls to the other stations using the same

modem can be completed. Otherwise the collection schedule will be delayed

waiting for the previous stations to finish.

RF networks with repeaters also add time delays since each modem must be

contacted and then pass the message on to the next RF modem and so on. Each

of these operations takes time so the time schedule for RF networks with

repeaters should allow enough time for the link to be established with the

datalogger and collect the data.

Consideration should also be given to other operations such as clock sets,

program downloads, or manual data requests to the datalogger. These require

significantly more time and can affect RF network responsiveness.

Any network setup using a phone to RF should be reviewed for collection

scheduling issues due to the combinations of time delays associated with RF

data collection.

4.2.5.3 Setting Up Scheduled Data Collection

The data to be collected and the output file locations and format are specified

on the datalogger’s Data File or Final Storage tab. The Schedule tab is used to

define the interval on which the LoggerNet server will check the datalogger for

new data. If new data exists, it will be stored in the data files and the

LoggerNet data cache.

To set up a data collection schedule for a datalogger, first ensure that your

device map has been configured with all of the devices listed as they actually

exist. Next, determine which tables or final storage areas should be collected

from the datalogger each time a data collection attempt is made. If no tables

are selected on the Data Files tab or the Final Storage Area is not enabled for

collection, no data will be collected from the datalogger.