E.1.3.3 communications status log format, E.1.3.3 – Campbell Scientific LoggerNet Datalogger Support Software User Manual

Page 550

Advertising
background image

Appendix E. Log Files

Transaction Log Example

"2009-04-15 16:41:05.367","CR1000","11","Clock check started"

"2009-04-15 16:41:05.429","CR1000","13","Clock checked","2009-04-15 16:41:33.44","2009-04-15 16:41:05.421","-28"

"2009-04-15 16:41:06.367","CR1000","86","Manual poll started","admin"

"2009-04-15 16:41:06.367","CR1000","92","Collect area poll started","TestFast"

"2009-04-15 16:41:06.382","CR1000","41","Records received","TestFast","21007","21007","polling"

"2009-04-15 16:41:06.382","CR1000","20","Hole detected","TestFast","20769","21006"

"2009-04-15 16:41:06.429","CR1000","11","Clock check started"

"2009-04-15 16:41:06.492","CR1000","41","Records received","TestFast","20769","20799","polling"

"2009-04-15 16:41:06.507","CR1000","144","data file opened","TestFast","C:\Campbellsci\LoggerNet\CR1000_TestFast.dat"

"2009-04-15 16:41:06.507","CR1000","21","Hole collected","TestFast","20769","20799"

"2009-04-15 16:41:06.507","CR1000","41","Records received","TestFast","20800","20864","polling"

"2009-04-15 16:41:06.507","CR1000","21","Hole collected","TestFast","20800","20864"

"2009-04-15 16:41:06.523","CR1000","13","Clock checked","2009-04-15 16:41:34.55","2009-04-15 16:41:06.516","-28"

"2009-04-15 16:41:06.601","CR1000","41","Records received","TestFast","20865","20899","polling"

"2009-04-15 16:41:06.601","CR1000","21","Hole collected","TestFast","20865","20899"

"2009-04-15 16:41:06.601","CR1000","41","Records received","TestFast","20900","20960","polling"

"2009-04-15 16:41:06.601","CR1000","21","Hole collected","TestFast","20900","20960"

"2009-04-15 16:41:06.648","CR1000","41","Records received","TestFast","20961","20999","polling"

"2009-04-15 16:41:06.648","CR1000","21","Hole collected","TestFast","20961","20999"

"2009-04-15 16:41:06.648","CR1000","41","Records received","TestFast","21000","21006","polling"

"2009-04-15 16:41:06.648","CR1000","21","Hole collected","TestFast","21000","21006"

"2009-04-15 16:41:06.679","CR1000","145","data file closed","TestFast","C:\Campbellsci\LoggerNet\CR1000_TestFast.dat"

"2009-04-15 16:41:06.679","CR1000","94","Collect area poll complete","TestFast","956","956"

"2009-04-15 16:41:06.695","CR1000","87","Manual poll complete"

"2009-04-15 16:41:07.429","CR1000","11","Clock check started"

"2009-04-15 16:41:07.445","CR1000","13","Clock checked","2009-04-15 16:41:35.46","2009-04-15 16:41:07.438","-28"

"2009-04-15 16:41:08.429","CR1000","11","Clock check started"

E.1.3.3 Communications Status Log Format

Each record in the communications status log includes two fields in addition to

the timestamp and device name:

Severity – A single character code that indicates the type of message. The

following values are legal:

“S” (Status) Indicates that the identified operation has successfully

completed.

“W” (Warning) Indicates that the server has attempted to retry the

operation with the identified device.

“F” (Fault) Indicates that the identified operation has failed and that the

server has stopped retrying.

Description – text providing more details about the event.

E-18

Advertising