Section 7. Creating and Editing Datalogger Programs

CR9000(X)/CR5000 Datalogger Run Now Options
The Run Now options and behavior for the CR9000(X) and CR5000

dataloggers are different from the CR1000, CR3000, and CR800 dataloggers.

Below is a dialog box for a CR9000X datalogger.

When Run Now is checked, the file will be sent with the Run Now attribute

set. With this attribute, the program is compiled and run in the datalogger. All

data tables on the CPU are erased. You have the option of whether or not to

erase data files stored on a card.

Run On Power-up

The file will be sent with the Run On Power-up attribute set. The program will

be run if the datalogger loses power and then powers back up.

Run Always

Run Now and Run On Power-up can both be selected. This sets the program's

file attribute in the datalogger as Run Always. The program will be compiled

and run immediately and it will also be the program that runs if the datalogger

is powered down and powered back up.

CR200 Datalogger Run Options

The CR200 does not have an on-board compiler. A compiled binary (*.bin)

file is sent to the datalogger. Run options are not applicable to this datalogger

and are therefore disabled.

Compress File

If the

Compress File check box is selected, a renamed version of the CRBasic

program which has all unnecessary spaces, indentation, and comments

removed in order to minimize the file size will be sent to the datalogger

instead of the original program.