Appendix E. Log Files

Communications Status Log Example

"2009-04-15 16:41:05.367","IPPort","S","Device dialed"

"2009-04-15 16:41:05.382","PakBusPort_ip","S","sending message","src: 4094","dest: 2","proto: PakCtrl","type: 0x09","tran: 214"

"2009-04-15 16:41:05.398","PakBusPort_ip","S","received message","src: 2","dest: 4094","proto: PakCtrl","type: 0x89","tran: 214"

"2009-04-15 16:41:05.398","CR1000","S","PakCtrl message received","89"

"2009-04-15 16:41:05.413","PakBusPort_ip","S","sending message","src: 4094","dest: 2","proto: BMP5","type: 0x17","tran: 213"

"2009-04-15 16:41:05.429","PakBusPort_ip","S","received message","src: 2","dest: 4094","proto: BMP5","type: 0x97","tran: 213"

"2009-04-15 16:41:05.429","CR1000","S","BMP5 message received","type: 0x97","check/set clock"

"2009-04-15 16:41:06.367","PakBusPort_ip","S","sending message","src: 4094","dest: 2","proto: BMP5","type: 0x09","tran: 217"

"2009-04-15 16:41:06.382","PakBusPort_ip","S","received message","src: 2","dest: 4094","proto: BMP5","type: 0x89","tran: 217"

"2009-04-15 16:41:06.382","CR1000","S","BMP5 message received","type: 0x89","table poll","CR1000.TestFast"

"2009-04-15 16:41:06.382","PakBusPort_ip","S","sending message","src: 4094","dest: 2","proto: BMP5","type: 0x09","tran: 218"

"2009-04-15 16:41:06.492","PakBusPort_ip","S","received message","src: 2","dest: 4094","proto: BMP5","type: 0x89","tran: 218"

"2009-04-15 16:41:06.492","CR1000","S","BMP5 message received","type: 0x89","table poll","CR1000.TestFast"

"2009-04-15 16:41:06.523","PakBusPort_ip","S","sending message","src: 4094","dest: 2","proto: BMP5","type: 0x17","tran: 219"

"2009-04-15 16:41:06.523","PakBusPort_ip","S","received message","src: 2","dest: 4094","proto: BMP5","type: 0x97","tran: 219"

TABLE E-2. Communication Status Log Messages

Message Text

Message Meaning

User Response to Message

Serial packet X exchanged

The low level serial

BMP1 communication

framing packet was sent

and the response

received from the device.

(CR10X-TD table based

type devices)

Classic;;Cmd

The listed command was

sent to an array based

datalogger.

For a list of the commands and their

meanings see the datalogger

operator’s manual.

BMP1 packet received

A BMP1 packet was

received from the device.

(CR10X-TD type

devices only)

RPC packet exchanged

A BMP3 packet was

exchanged. (CR5000,

CR9000 dataloggers

only)

Datalogger did not respond to

end command

The computer tried to

terminate the connection

but the datalogger did

not acknowledge the

shutdown.

This is an indication that there is a

communications problem between

the computer and the datalogger.

Check the cables and connectors

and make sure the datalogger has

power.