8 rfremote, Rfremote -26 – Campbell Scientific LoggerNet Datalogger Support Software User Manual

Page 82

Advertising
background image

Section 4. Setting up Datalogger Networks

If you are using LoggerNet Admin or LoggerNet Remote 4.0 and

using the Connect Screen to connect to a remote server that is

running an older version of LoggerNet, the behavior will be

different than described above. When connecting to a LoggerNet

3.4.1 server, you will be disconnected with no advanced warning

when Max Time On-Line is reached. A message will be displayed

indicating that Max Time On-Line has been reached. When

connecting to servers older than LoggerNet 3.4.1, the behavior

will be variable. Generally, you will be disconnected at some

point, but the timing of the disconnect will not be predictable.

Maximum Baud Rate – Select the arrow to the right of this field to choose a

maximum baud rate for communication with this device. Note that the actual

rate of communication may be limited by the capability of other devices in the

communications chain.

Advanced
Extra Response Time – In this field, specify the additional time that

LoggerNet should delay before terminating the communications link if there is

no response from the RFBase. Additional time may be needed in instances

where the communications link is noisy or network traffic is heavy.

Maximum Packet Size – Data is transferred in “chunks” called packets. For

most devices the default value is 2048 byes. The value entered in this field can

be changed in 32 byte increments. If a communications link is marginal,

reducing the packet size may improve reliability.

Delay Hangup – The amount of time, in seconds and milliseconds, that

LoggerNet should delay before hanging up the link to the device. If a new

command to the device is issued before the delay has expired, communication

will not be terminated.

The RFBase device is not used for RF400 radios.

4.2.4.8 RFRemote

The RF remote has only Hardware and Notes tabs.

Standard
Communications Enabled – Before communications can take place, all

devices in the chain must have the Communications Enabled box checked.

When this box is selected, communication to the RF modem is enabled.

Address – The hardware for each RF modem is configured for a certain

address with internal switches. This address acts as an identification for the

device in an RF network. Each RF modem in the network must have a unique

address; this number is entered in the Address field. Each RF modem used as a

repeater only site still needs its own unique Address.

NOTE

NOTE

4-26

Advertising