Section 5. Real-Time Tools

Once the datalogger connection is established, an elapsed time for the

connection will be shown on the bottom left of the window. This counter will

continue as long as the datalogger connection is maintained. The user should

be aware of the how long the Connect Screen is connected to the datalogger. A

manually initiated connection to a datalogger takes priority over other

communication in the network map. Other devices that share any part of the

communication path will not be contacted, even for scheduled data collection.

Once a connection is made to a datalogger with the Connect

Screen, this connection takes precedence and will prevent

communication with other devices sharing the same serial port or

base modem.

To disconnect from the datalogger, click the button that now reads Disconnect.

To work with another datalogger you must disconnect from the first one

(unless you have installed LoggerNet Admin or LoggerNet Remote). Double

clicking another datalogger will disconnect from the first datalogger and

connect to the new one without prompting.

If LoggerNet fails to make a connection to the datalogger, it will time out and

display an error message that it could not connect. It will immediately attempt

the connection again and will continue trying until the user clicks Cancel.

5.1.2 Data Collection

The Collect Now and Custom buttons of the Connect Screen allows you initiate

a manual data collection from the datalogger. LoggerNet keeps track of two

separate data collection pointers for each datalogger: (1) the pointer for

scheduled data collection and manual data collection from the Connect

Screen’s Collect Now button, and (2) the pointer for manual data collection

from the Custom Collection window.

The data for each of these two pointers is, by default, stored in two separate

data files on the computer. The default directory for scheduled data

collection/manual data collection is C:\Campbellsci\LoggerNet. The default

directory for data collection via the Custom Collection window is

C:\Campbellsci\LoggerNet\Data. Because different pointers are kept in

LoggerNet for each of these collection options, if you select Collect Now from

the main Connect Screen, and your Setup option is set to collect only new data,

and then you do a Custom Collection and also choose to collect only new data,

the new data collected using the Custom Collection window is the new data

since the last time you collected using this window. Similarly, new data

collected using Collect Now from the main Connect Screen is the new data

since the last time you chose Collect Now, or since the last scheduled data

collection.

5.1.2.1 Collect Now

The Collect Now function is the equivalent of doing a scheduled data

collection for the datalogger without waiting for the scheduled time. Clicking

the Collect Now button will initiate a call to the datalogger and any available

data will be collected and stored as specified on the Setup Screen. This

function is often used to manually update data collection to see the latest data

in a Numeric Display or a Graph; or before data files are copied for processing.

NOTE

5-3