Campbell Scientific LoggerNet Datalogger Support Software User Manual

Page 58

Advertising
background image

Section 4. Setting up Datalogger Networks

Subsequent pages are similar. Previous and Next buttons are provided to move

through each step of the wizard. Progress is shown by the blue arrow next to

each step displayed at the left. Field descriptions and helpful tips are displayed

on the wizard page. If additional help is needed, the on-line help can be

opened by pressing F1 or the Help button on the bottom right of each page.

In the Communication Setup step you first select the datalogger type and give

it a name. (This name will also become the default file name for data files

collected from that datalogger.) Next you choose the connection type from the

possible communications methods supported for that datalogger. EZSetup

Wizard fills in as many communications settings as possible; in many cases

you can use the default settings. It also provides fields for user-entered

communications settings such as phone numbers and RF radio addresses.

The Datalogger Settings step is provided for fine tuning the connection to the

datalogger. The baud rate offered is typically the maximum baud rate

supported by that datalogger and communications medium; lower rates may be

required for cell phones or noisy telephone links. Enter a Security Code only if

the datalogger is configured – via the keyboard/display or settings in the

datalogger program – to use it. Note that the default Max Time On-Line

setting for most communications links is zero (“0 d 00 h 00 m”), which means

that LoggerNet will never hang up until you click

Disconnect. For telephone

links, the default Max Time On-Line setting is 10 minutes in order to reduce

the possibility of inadvertent and expensive long distance or cellular telephone

charges. There are, however, other links that can result in expensive

connection charges, such as digital cellular links using TCP/IP that charge by

the byte. Leaving the datalogger connected also uses battery power, so if the

datalogger power supply is not recharged from a reliable source, it may

discharge its battery below safe levels. Be sure, therefore, that you do not

leave the datalogger connected beyond the time necessary to do the tasks you

need to do.

The Setup Summary step provides a list of the settings entered. You can use

the Previous button to return to a page and change these settings if necessary.

The Communications Test step allows you to test the communications link

before going any further. If the datalogger is not installed, you can skip this

and the next two steps.

If communication succeeds, you can move to the Datalogger Clock step where

you can check or set the datalogger’s clock to match the PC’s system time. If

the datalogger is in a different time zone, you can enter an offset in hours and

minutes.

The Send Program step allows you to send a program to the datalogger. This

may be a program you created with Short Cut, Edlog or the CRBasic Editor or

a program supplied by someone else. If it is a mixed-array datalogger, and the

datalogger is already running a program, you should associate the .DLD file so

that LoggerNet will use the labels for input locations and final storage.

Dataloggers with table-based operating systems (TD, PakBus, and CRx000)

will know their program if one is running and will provide table definitions that

contain the labels. If you don’t have a program for the datalogger you can skip

this step and send a program later from the Setup Screen or Connect Screen.

The Data Files step is where you define what data tables, or final storage areas,

should be collected by LoggerNet and saved to disk. If you used the EZSetup

4-2

Advertising