A.2.7

Standstill monitoring

With the standstill monitoring it is clear that the target
position window is exited at a standstill.

When the target position is reached and the MC signal is
registered the drive enters the Standstill" status, the bit
Standstill_Control is reset. If, in this status, the drive is
removed from the standstill position window for a minimum
defined time due to external forces or other influences, the bit
Standstill_Control will be set.

As soon as the drive is in the standstill position window again
for the standstill monitoring time, the bit Standstill_Control
will be reset.

1

Target position

2

Actual position

3

Standstill monitoring
(Standstill_Control)

4

Motion Complete
(MC)

5

Standstill position
window

6

Target position
window

7

Monitoring time
(position window
time)

8

Standstill monitoring
time

1

0

1

0

1

2

3

4

5 6

7

8

8

Fig. A/7:

Standstill monitoring

The standstill monitoring cannot be switched on or off exĆ
plicitly. It becomes inactive when the standstill position winĆ
dow is set to the value 0".