SECTION 6 - JLG CONTROL SYSTEM

6-40

– JLG Lift –

3121287

MAIN DUMP VALVE – OPEN
CIRCUIT

3359

The Ground Module detects an open circuit at the Main Dump Valve
output.

No response required.

Check for a good connection at
the solenoid and for continuity
through this circuit. With the
solenoid disconnected, an
open circuit voltage of nearly
8.0V exists on the Ground Mod-
ule output pin for diagnostic
purposes. Inspect wiring for
physical damage. Cycle power
to clear the fault.

MAIN DUMP VALVE – SHORT
TO BATTERY

3360

The Ground Module detects a short to battery at the Main Dump
Valve output.

Ground Module Main Dump,
Swing Left/Right, Telescope,
and Lift Up outputs are dis-
abled.

Inspect wiring for physical
damage and check for wire
continuity. Cycle power to clear
the fault.

BRAKE – SHORT TO GROUND

3361

The Ground Module detects a short to ground at the Brake output.

Ground Module Drive/Steer
and Brake outputs are disabled.

Inspect wiring for physical
damage and check for wire
continuity. Cycle power to clear
the fault.

START SOLENOID – SHORT TO
GROUND

3362

The Ground Module detects a short to ground at the Engine Starter
Solenoid.

Engine Start attempt is not per-
mitted.

Inspect wiring for physical
damage and check for wire
continuity. Cycle power to clear
the fault.

START SOLENOID – OPEN CIR-
CUIT

3363

Ground Module detects an open circuit at this output.

No response required.

Inspect wiring for physical
damage and check for wire
continuity. Cycle power to clear
the fault.

START SOLENOID – SHORT TO
BATTERY

3364

The Ground Module detects a short to battery at the Engine Starter
Solenoid.

Ground Module Engine Start is
disabled.

Inspect wiring for physical
damage and check for wire
continuity. Cycle power to clear
the fault.

STEER DUMP VALVE – SHORT
TO GROUND

3365

The Ground Module detects a short to ground at the Steer Dump
Valve output.

Ground Module Steer Dump
output is disabled.

Inspect wiring for physical
damage and check for wire
continuity. Cycle power to clear
the fault.

STEER DUMP VALVE – OPEN
CIRCUIT

3366

The Ground Module detects an open circuit at the Steer Dump Valve
output.

No response required.

Check for a good connection at
the solenoid and for continuity
through this circuit. With the
solenoid disconnected, an
open circuit voltage of nearly
8.0V exists on the Ground Mod-
ule output pin for diagnostic
purposes. Inspect wiring for
physical damage. Cycle power
to clear the fault.

Table 6-5. Fault Code Troubleshooting Information

Help Message

DTC

Condition Producing DTC

Control System Response or

Machine Condition

Corrective Action/

Operational Requirement

for Function Movement

and/or to Clear Fault