SECTION 6 - JLG CONTROL SYSTEM

6-50

– JLG Lift –

3121287

ENGINE TROUBLE CODE

437

The engine controller reports a J1939 fault

Engine will operate at
1800RPM until power cycle.

Cycle power to clear the fault.

HIGH ENGINE TEMP

438

For a machine configured with a Kubota D1105 engine, the engine
has been running more than 10 seconds and the engine coolant tem-
perature is greater than 110ºC:

For a machine with electronic engine controls, the ECM transmits an
engine coolant high temperature critical fault (SPN:FMI 110:0)

If MACHINE SETUP

 ENGINE

SHUTDOWN = ENABLED then
the engine will be shut down
and the High Engine Tempera-
ture indicator will be lit

Reduce hydraulic loading of
machine and inspect radiator
for blockage of air flow.

NO ALTERNATOR OUTPUT

4310

The engine has been running more than 10 seconds and Ground
Module system voltage is less than 11.5 volts for 10 seconds

The No Charge indicator will be
lit

Ground Module system voltage
greater than 11.7 volts

LOW OIL PRESSURE

4311

For a machine configured with a Kubota D1105 engine, the engine
has been running more than 10 seconds and the engine oil pressure is
LOW (debounce 3s).
For a machine with electronic engine controls, the ECM transmits an
engine oil low pressure critical fault (SPN:FMI 100:1).

If MACHINE SETUP

 ENGINE

SHUTDOWN = ENABLED then
the engine will be shut down
and the Low Oil Pressure indi-
cator will be lit

Check engine oil level. Cycle
power to clear the fault.

THROTTLE ACTUATOR FAILURE

4313

For a machine configured with a Kubota D1105 engine:
THROTTLE ACTUATOR – OPEN CIRCUIT (33131) is not active
THROTTLE ACTUATOR – SHORT TO GROUND (33130) is not active
LOSS OF ENGINE SPEED SENSOR (4322) is not active
desired engine speed is greater than 1800 but actual RPM is less than
1400 (debounce time = 3s) when no fault exists with Proportional
Fuel Rack actuator

Disable Ground Module Throt-
tle Actuator output and call for
full opening (current =
1500mA) to Proportional Fuel
Rack Actuator.

Cycle power to clear the fault.

WRONG ENGINE SELECTED –
ECM DETECTED

4314

Machine is configured with a non-electronic controlled Kubota
D1105 engine and the Ground Module detects an electronic engine
controller on the CAN bus

No function inhibits required

Cycle power to clear the fault.

LOSS OF ENGINE SPEED SEN-
SOR

4322

Machine is configured with a Kubota D1105 engine and the engine is
running:
LOW OIL PRESSURE fault (4311) is not active
OIL PRESSURE SHORT TO BATTERY fault (433) is not active
No engine shutdown command exists
Engine RPM is read as 0 for 1500ms and Engine oil pressure is not LOW

Ground Module to limit all
function speeds to creep, but
run at High Engine speed until
the oil pressure drops to a low
value. Ground Module to dis-
able Generator relay output
until generator operator switch
cycled.

Check proper seating/clear-
ance of engine speed sensor
installation. Verify continuity
of wiring before replacing sen-
sor. Fault cleared when Engine
RPM greater than 0

SPEED SENSOR READING
INVALID SPEED

4323

Machine is configured with a Kubota D1105 engine and the engine
RPM reading is greater than 4000

The Ground Module commands
High Engine speed and places
all functions in Creep.

Verify integrity of wiring, par-
ticularly the ground, before
replacing sensor. Fault cleared
when engine RPM reading <
4000

FUEL ACTUATOR – SHORT TO
GROUND

4326

The Ground Module detects a short to ground at the fuel actuator
output. (Kubota)

The Ground Module disables
the Fuel Actuator output

Inspect wiring for physical
damage and check for wire
continuity. Check for coil dam-
age or shorting condition in
connector. Cycle power to clear
the fault.

Table 6-5. Fault Code Troubleshooting Information

Help Message

DTC

Condition Producing DTC

Control System Response or

Machine Condition

Corrective Action/

Operational Requirement

for Function Movement

and/or to Clear Fault