Electrical System

9-8

3706PS, 3707PS, 4014PS, 4017PS, 33.7, 37.6, 37.7

9.5.3

Calibration

Bucket
Telescope

Allows the owner to adjust the Max Bucket Tele In and Max
Bucket Tele Out function speeds

1300 mA

Bucket Tilt

Allows the owner to adjust the Max Bucket Tilt Up and Max
Bucket Tilt Down function speeds

1400 mA (up)

1600 mA (down)

Auxiliary
Function

Allows the owner to adjust the Accel, Decel, and Max Function
Coil A and Max Function Coil B function speeds

1500 mA

Function

Description

Default Value

Menu

SubMenu

Visible

Comment

Calibrations:
Tilt Sensor

Calibrate Tilt
Sensor?

Access Levels
1,2;
Machine Setup’s
PLATFORM
OPTION is
ENABLED

Use by technicians to calibrate the tilt sensor (integral
to UGM); press ENTER to confirm; ESC to exit

Tilt Calibration
Set Stabilizers

Displayed when Machine Setup’s STABILIZERS is
EQUIPPED and at least one stabilizer is not deployed;
press ENTER or ESC to exit

Tilt Sensor
Calibrating...

Displayed while control system averages readings

Calibration
Complete

Calibration offset was within +/- 8.0 degrees; press
ENTER or ESC to exit

Calibration Failed

Calibration offset was outside +/- 8.0 degrees; press
ENTER or ESC to exit