Electrical System

9-78

3706PS, 3707PS, 4014PS, 4017PS, 33.7, 37.6, 37.7

PLATFORM

MODULE

HARDWARE

FAILURE

9948

5000mS

·Hydraulic functions are prevented in

Platform Mode

·Engine Start is prevented is Platform

Mode

Machine Setup’s PLATFORM

OPTION is ENABLED; Platform

Module reports a Low sense FET

failure

Power cycled

MACHINE

CONFIGURATI

ON OUT OF

RANGE –

CHECK ALL

SETTINGS

9949

Continuously

·Hydraulic functions are prevented

·Engine Start is prevented

·UGM J4-12 ECM / Fuel Relay is

energized to shutdown engine

UGM detects a parameter range or

checksum issue with Machine Setup

Machine

Setup is
properly

configured;

Power cycled

CABIN

JOYSTICK -

INTERNAL

FAILURE

9976

Continuously

·Hydraulic functions are prevented

·Direction selection shall be neutral

·

·Cabin Mode; cabin joystick

transmits a DM1 (SPN:FMI)

with 520192:13 or 520193:13

·Cabin Mode; cabin joystick

transmitted an undocumented DM1

(SPN:FMI)

Power cycled

LSS CORRUPT

EEPROM

9977

Continuously

·Platform assumed to be overloaded

·Hydraulic functions are prevented

Platform attached; Load Sensing

System is configured;

control system detects parameter

range or checksum issue

Power cycled

EEPROM

VALUE – OUT

OF RANGE

9978

Continuously

·Hydraulic functions are prevented

·Engine Start is prevented

·UGM J4-12 ECM / Fuel Relay is

energized to shutdown engine

UGM detects a parameter range or

checksum issue with Personalities

Personalities

are properly

configured;

Power cycled

GROUND

MODULE VLOW

FET FAILURE

9986

Continuously

·Hydraulic functions are prevented

·Engine Start is prevented

·UGM J4-12 ECM / Fuel Relay is

energized to shutdown engine

UGM detects a Low sense FET

failure

(all high-sensing digital inputs are

high)

Power cycled

FUNCTIONS

LOCKED OUT –

LSI SOFTWARE

VERSION

IMPROPER

99151

Continuously

Load Moment Cutout assumed to be

100%

Load Monitoring configured;

LSI System transmitted Major /

Minor Software version that is not

compatible (P0.11 or greater; P1.x

allowed)

Power cycled

LSI FAULTY –

SYSTEM

FLASH CRC

ERROR

99152

Continuously

Load Moment Cutout assumed to be

100%

Load Monitoring configured;

LSI System reports Fault #1 – CRC

Error in System Flash

Power cycled

LSI FAULTY –

DATA FLASH

CRC ERROR

99153

Continuously

Load Moment Cutout assumed to be

100%

Load Monitoring configured;

LSI System reports Fault #2 – CRC

Error in Data Flash

Power cycled

LSI FAULTY –

LOAD CELLS A

AND B

DISAGREEMEN

T

99154

Continuously

Load Moment Cutout assumed to be

100%

Load Monitoring configured;

LSI System reports Fault #3 –

Excessive Data Variance between

Load Cell A and Load Cell B

Power cycled

Advertising