Electrical system – JLG 4017PS Service Manual User Manual

Page 219

Advertising
background image

9-61

3706PS, 3707PS, 4014PS, 4017PS, 33.7, 37.6, 37.7

Electrical System

d. Output Drivers (33X)

PLATFORM

ATTACHED ANGLE

LIMIT EXCEEDED

2533

Continuously

Lift Up is prevented

Machine Setup’s PLATFORM

OPTION is ENABLED; platform is

attached; Platform Module

detected that the boom angle

exceed the Overshoot Angle

UGM and

Platform

Module

confirm the

boom angle is

less than the

Cutout Angle

for 1,000mS

SYSTEM TEST
MODE ACTIVE

2548

5000mS

Boom functions, Stabilizer, and

Frame Leveling are prevented

Engine Start is prevented

System Test has been activated

using the Analyzer or Cabin

Display

Power cycle

BOOM EXTENSION

LIMIT SWITCHES –

CONFLICTING

STATES

2557

5000mS

Telescope Out is prevented in

Platform Mode

Lift Down is prevented until the

boom is fully retracted (UGM J3-8)

in Platform Mode

Platform Mode is prevented

Machine Setup’s PLATFORM

OPTION is ENABLED; MODEL is

4017; Boom Extension Limit

Switch 1 (UGM J7-8) and Switch 2

(AM J1-4) disagree for more than

500mS while Telescope is active

Power cycle

TELESCOPE

POSITION

SWITCHES –

CONFLICTING

STATES

2558

5000mS

Platform Mode is prevented

Machine Setup’s PLATFORM

OPTION is ENABLED; platform

attached; MODEL is 4017; Boom

Extension Limit Switch 1 (UGM J7-

8) and Switch 2 (AM J1-4) indicate

Critical (de-energized); Boom
Retracted Switch (UGM J3-8)

indicates Retracted (energized)

Power cycle

BOOM

RETRACTED

SENSOR FAULTY –

SENSING INVALID

2560

Continuously

Boom extended (ignore J3-8 Boom

Retracted Switch)

Machine Setup’s BOOM
RETRACT is YES and the J3-8
Boom Retracted Switch becomes
unhealthy

Power cycled

or boom

retracted

switch

becomes

healthy

FUNCTIONS

LOCKED OUT –

TCM CONSTANT

DATA VERSION

IMPROPER

2562

Continuously

Boom functions, Auxiliary A/B,

Stabilizer, and Frame Leveling are

prevented

Engine Start is prevented

TCM Constant Data version does

not agree with Application

Re-program

TCM;

Power cycled

OUTPUT

DRIVERS

33XXX

-

-

-

-

MAIN LIFT UP

VALVE – OPEN

CIRCUIT

33181

5000mS

Lift Up is prevented

Open-circuit is detected on UGM

J2-11

Power cycled

MAIN LIFT VALVES

– SHORT TO

BATTERY

33182

Continuously

Lift Up is prevented

Lift Down is prevented

UGM J3-2 Lift Return is disabled

Short to battery is detected on

UGM J2-11 or UGM J2-22

Power cycled

MAIN LIFT UP

VALVE – SHORT

TO GROUND

33183

Continuously

Lift Up is prevented

Lift Down is prevented

UGM J3-2 Lift Return is disabled

Short to ground is detected on

UGM J2-11

Power cycled