Before building the configuration database, the operator must know
exactly what hardware is used in the system.

System type — Eagle 2000 or Eagle Quantum?
How many LONs are being used?
How many and what type of field devices?

Input devices:

Flame detectors — UV, UV/IR
Gas Detectors — DCU with combustible, H2S, PointWatch, etc.

IDCs

Output devices:

SAMs
ARMs

Power supply monitors
Gateways

Main gateway (required)
Auxiliary gateways (up to 3)

Logic Controllers

Power supplies
LIOU

Release boards
Sounder boards
Relay boards

After determining the type and number of field devices, each device
must be assigned an address.

• Main gateway must be address 1.
• Addresses 2 to 4 are reserved for auxiliary gateways.
• Logic controllers occupy two adjacent addresses. They are assigned

an odd address and automatically assume the following even
address. For convenience it is recommended to work up from
address 5.

• The remaining addresses are available for field devices.

NOTE

The gateway relays are programmed to monitor a “block” of
addresses. Take this into account when selecting addresses for
field devices.

1. To start a new database, select “New” under the “File” menu.

2. To save the project, select “Save” under the “File” menu. If the file

has not been named, select “Save As,” name the file, and save.

95-8479

3.1

C

ONFIGURATION AND

S

YSTEM

M

ONITORING

O

VERVIEW

B

UILDING A

D

ATABASE

S

TARTING A

N

EW

D

ATABASE